Table 11 – Rockwell Automation 150 SMC Quick Start Manual User Manual
Page 37
Advertising
Rockwell Automation Publication 150-QS003D-EN-P - November 2013
35
Programming Chapter 3
Table 11 - Rotary Switch Position Settings & Resulting Values — Ramp and Stop
Time Configurations
S3 = Ramp Time Configuration — Starting — Controller Parameter 50
Position Setting Starting Ramp Time [s]
Position Setting Starting Ramp Time [s]
0
0.1
8
16
1
2
9
18
2
4
A
20
3
6
B
22
4
8
C
24
5
10 (default)
D
26
6
12
E
28
7
14
F
30
S4 = Stop Time Configuration — Controller Parameter 66
Position Setting Stop Time [s]
➊
Position Setting Stop Time [s]
➊
0
Coast -to-Stop (default)
8
16
1
2
9
18
2
4
A
20
3
6
B
22
4
8
C
24
5
10
D
26
6
12
E
28
7
14
F
30
➊
When the braking STOP MODE is selected (device configuration bank switch #3 and #4), the
controller multiplies the selected stop time by ten.
Advertising