Table 11 – Rockwell Automation 150 SMC Quick Start Manual User Manual

Page 37

Advertising
background image

Rockwell Automation Publication 150-QS003D-EN-P - November 2013

35

Programming Chapter 3

Table 11 - Rotary Switch Position Settings & Resulting Values — Ramp and Stop
Time Configurations

S3 = Ramp Time Configuration — Starting — Controller Parameter 50

Position Setting Starting Ramp Time [s]

Position Setting Starting Ramp Time [s]

0

0.1

8

16

1

2

9

18

2

4

A

20

3

6

B

22

4

8

C

24

5

10 (default)

D

26

6

12

E

28

7

14

F

30

S4 = Stop Time Configuration — Controller Parameter 66

Position Setting Stop Time [s]

Position Setting Stop Time [s]

0

Coast -to-Stop (default)

8

16

1

2

9

18

2

4

A

20

3

6

B

22

4

8

C

24

5

10

D

26

6

12

E

28

7

14

F

30

When the braking STOP MODE is selected (device configuration bank switch #3 and #4), the

controller multiplies the selected stop time by ten.