Warning – Rockwell Automation 140U H-Frame Circuit Breaker Fixed and Adjustable Thermal Trip User Manual

Page 2

Advertising
background image

Effective 01/01

4

5

3

10 in-lb (0.2 N m)

34-38 in-lb (3.8-4.3 N m)

10 in-lb (0.2 N m)

ON

TRIP

OFF

RESET

Push to trip

6

Warning

INSTALL WIRE APPLICABLE
TO THE HIGHEST RATING
SHOWN ON BREAKER.

Note: Mounting hardware included. Use nuts (provided)

if not threading holes in mounting surface.

Note: Endcap is sold separately.

Optional thermal adjustment

H Frame Collar Torque Values

Wire Size

Torque

AWG

(mm

2

)

In-lb

(N

m)

14-10 (2.5-6)

35

(4.0)

8

(10)

40

(4.5)

6-4

(16-25)

45

(5.1)

3-3/0

(35-95)

50

(5.6)

Note: If cover must be

removed for accessory

installation, torque

cover mounting screws

to 6-8 in-lb (.7-.9 N

m).

40752-001

Effective 02/02

Advertising