Adapter parameters, Parameter list, Appendix b – Rockwell Automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter User Manual

Page 119: Appendix

Advertising
background image

Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013

119

Appendix

B

Adapter Parameters

Appendix B provides information about the parameters used to configure the
embedded EtherNet/IP adapter.

Parameter List

The parameters are displayed in a Numbered List view order.

Topic

Page

Parameter List

119

Parameter

No.

Name and Description

Details

C121

[Comm Write Mode]
Saves parameter values in active drive memory (RAM) or in
drive non-volatile memory (EEPROM).
Important: Parameter values set prior to setting 1 “RAM only”
are saved in RAM.

Default:

0 = Save

Values:

0 = Save
1 = RAM only

Type:

Read/Write

Reset Required:

C122

[Cmd Stat Select]
Selects velocity-specific or position/fibers-specific Command
and Status Word bit definitions for use over a communication
network.
This parameter cannot be changed when an I/O connection is
established through the communication adapter or the drive’s
embedded EtherNet/IP port.

Default:

0 = Velocity

Values:

0 = Velocity
1 = Position

Type:

Read/Write

Reset Required:

Yes

C123

[RS485 Data Rate]
Sets the communications baud rate (bits/second) for the RS485
port. A reset or power cycle is required after selection is made.

Default:

3 = 9600

Values:

0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400

Type:

Read/Write

Reset Required:

Yes

C124

[RS485 Node Addr]
Sets the Modbus drive node number (address) for the RS485
port if using a network connection. A reset or power cycle is
required after selection is made.

Default:

100

Minimum:

1

Maximum:

247

Type:

Read/Write

Reset Required:

Yes

C125

[Comm Loss Action]
Sets the drive's response to a loss of connection or excessive
communication errors on the RS485 port.

Default:

0 = Fault

Values:

0 = Fault
1 = Coast Stop
2 = Stop
3 = Continu Last

Type:

Read/Write

Reset Required:

No

C126

[Comm Loss Time]
Sets the time that the drive remains in communication loss with
the RS485 port before taking the action specified in C125
[Comm Loss Action].
Important: This setting is effective only if I/O that controls the
drive is transmitted through the RS485 port.

Default:

5.0 s

Minimum:

0.1 s

Maximum:

60.0 s

Type:

Read/Write

Reset Required:

No