160-NX3 Series C Drive

Control Inputs

Control Inputs (Analog Signal Follower Model Only)

Control Inputs (Preset Speed Model Only)

Control Output

Control Features

Control Input Type

For dry contact closure input - drive has an internal 12V power supply that provides 10mA (typical)
current. Also accepts open collector/solid-state input with maximum leakage current of 50µA.
Optional 24V DC interface allows use of 24V DC “sink logic” inputs.

Start, Stop, Forward/Reverse

Configurable inputs for 2 or 3 wire control

Analog Input (4 to 20mA)

Input impedance 250 ohms

Analog Input (-10 to +10V DC)

Input impedance 100k ohms

External Speed Potentiometer

1k to 10k ohms, 2 Watt minimum

PI Control

Users of Firmware Version FRN 7.05 and earlier use Parameter 46 setting 9 to activate the PI
Control function.
Users of Firmware Version FRN 7.06 can use Parameter 46 settings 0 through 7 and 9 to activate
the PI Control function.

SW1, SW2

Parameter 46, setting 8 provides 4 preset speeds and 2 accel/decel times

SW1, SW2, SW3

Configurable inputs for control of 8 preset speeds and 2 accel/decel times

Programmable Output

(from C relay contact)

Resistive Rating: 0.4A at 125V AC, 0.2A at 230V AC, 2A at 30V DC
Inductive Rating: 0.2A at 125V AC, 0.1A at 230V AC, 1A at 30V DC
Programmable for eleven different functions

PWM Algorithm

Sine weighted PWM with harmonic compensation

Switching Device

(3-Phase Output)

IGBT (Insulated Gate Bipolar Transistor)

V/Hz Ratio

Programmable

Carrier Frequency

Adjustable from 2 kHz to 8 kHz in 100 Hz increments (factory default is 4 kHz)

DC Boost

Adjustable - Select from a family of boost curves

Current Limiting

Trip free operation, coordinated for drive and motor protection. Programmable from 1% to 180%
of drive Output Current.

Motor Protection

I

2

t overload protection - 150% for 60 seconds, 200% for 30 seconds (Provides Class 10 overload

protection). Percentage refers to Parameter 42 setting.

Overload Pattern #0

Flat response over speed range (no speed compensation)

Overload Pattern #1

Speed compensation below 25% of base speed

Overload Pattern #2

Speed compensation below 100% of base speed

Acceleration/Deceleration Time(s)

0.1 to 600 seconds

S-Curve Accel/Decel Time(s)

0 to 100% of accel/decel time - not to exceed 60 seconds

Stopping Models

4 modes (programmable)

Ramp to Stop

0.1 to 600 seconds

Coast

Stops all PWM output

DC Injection Brake

Applies DC voltage to the motor for 0 to 25 seconds

DC Injection Braking w/ Auto Stop

Applies DC voltage to the motor for 0 to 25 seconds with Auto Shutoff