GUIDE SPECIFICATIONS

GENERAL

System Description
Outdoor--mounted, air--cooled, split--system heat pump unit

suitable for ground or rooftop installation. Unit consists of a

hermetic compressor, an air--cooled coil, propeller--type

condenser fan, and a control box. Unit will discharge supply

air upward as shown on contract drawings. Unit will be used in

a refrigeration circuit to match up to a packaged fan coil or coil

unit.
Quality Assurance

— Unit will be rated in accordance with the latest edition

of ARI Standard 240.

— Unit will be certified for capacity and efficiency, and

listed in the latest ARI directory.

— Unit construction will comply with latest edition of

ANSI/ ASHRAE and with NEC.

— Unit will be constructed in accordance with UL

standards and will carry the UL label of approval.

Unit will have C--UL approval.

— Unit cabinet will be capable of withstanding Federal

Test Method Standard No. 141 (Method 6061) 500--hr

salt spray test.

— Air--cooled condenser coils will be leak tested at 217

psig and pressure tested at 450 psig.

— Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

— Unit will be shipped as single package only and is

stored

and

handled

per

unit

manufacturer’s

recommendations.

Warranty (for inclusion by specifying engineer)

— U.S. and Canada only.

PRODUCTS

Equipment

— Factory assembled, single piece, air--cooled heat

pump unit. Contained within the unit enclosure is all

factory

wiring,

piping,

controls,

compressor,

refrigerant charge (R--22), and special features

required prior to field start--up.

Unit Cabinet

— Unit cabinet will be constructed of galvanized steel,

bonderized, and coated with a powder coat paint.

Fans

— Condenser fan will be direct--drive propeller type,

discharging air upward.

AIR--COOLED, SPLIT--SYSTEM HEAT PUMP

213R

1--1/2 TO 5 NOMINAL TONS

— Condenser fan motors will be totally enclosed,

1--phase type with class B insulation and permanently

lubricated bearings.

— Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically

balanced.

— Condenser fan openings will be equipped with steel

wire safety guards.

Compressor

— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration

isolators.

Condenser Coil

— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins

mechanically bonded to copper tubes which are then

cleaned, dehydrated, and sealed.

Refrigeration Components

— Refrigeration

circuit

components

will

include

liquid--line shutoff valve with sweat connections,

vapor--line shutoff valve with sweat connections,

system charge of refrigerant, compressor oil,

accumulator, loss of charge switch, and reversing

valve.

Operating Characteristics

— The capacity of the unit will meet or exceed _____

Btuh at a suction temperature of _____ _F. The power

consumption at full load will not exceed _____ kW.

— Combination of the unit and the evaporator or fan coil

unit will have a total net cooling capacity of _____

Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F wet bulb

and _____ _F dry bulb, and air entering the unit at

_____ _F.

— The system will have a SEER of _____ Btuh/watt or

greater at DOE conditions.

Electrical Requirements

— Nominal unit electrical characteristics will be _____ v,

single phase, 60 hz. The unit will be capable of

satisfactory operation within voltage limits of _____ v

to _____ v.

— Nominal unit electrical characteristics will be _____ v,

three phase, 60 hz. The unit will be capable of

satisfactory operation within voltage limits of _____ v

to _____ v.

— Unit electrical power will be single point connection.
— Control circuit will be 24v.

Special Features

— Refer to section of this literature identifying

accessories and descriptions for specific features and

available enhancements.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.