Caution – Rockwell Automation 140U Instructions for Padlockable Handle Lock Hasp Installation User Manual

Page 2

Advertising
background image

Page

2

Figure 2- 1 Padlockable Handle Lock Hasp Installation

SPECIAL ATTENTlON SHOULD BE PAID TO

REVERSE FEED APPLICATIONS TO ENSURE NO

VOLTAGE IS PRESENT. THE VOLTAGES IN ENER-
GIZED EQUIPMENT CAN CAUSE DEATH OR
SEVERE PERSONAL INJURY.

Note:

When the padlockable handle lock hasp is

mounted on the circuit breaker cover, part of the
nameplate information is covered. Before mounting
the hasp, make sure that the information is recorded

for future reference. A blank nameplate is supplied
to record hidden information. The nameplate
should be placed on the side of the circuit breaker
or another convenient location adjacent to the cir-
cuit breaker.

The following steps describe how to mount the pad-

lockable handle lock hasp in the left-pole position

of the circuit breaker. The same procedure is used
for mounting the hasp in the right pole position.

2-1.

Mounting holes are located in the cover under the

nameplate. Find the mounting holes using the
locating marks in the nameplate. (See Fig.

2-1 .)

2-2...

Using a pencil or similar pointed tool, punch

through the area of the nameplate covering holes

2

and 3

(4

and

5

for right hand mounting).

2-3.

For mounting over the left pole, letter L on

mounting plate must be toward the line end of the

circuit breaker (Fig. 2-2). For mounting over the

right pole, letter R

must be toward the line end of the

circuit breaker.

2-4.

Position mounting plate on cover. Align mounting

holes. (See Fig. 2-2).

CAUTION

FIRMLY TIGHTEN, BUT DO NOT OVERTIGHTEN,
MOUNTING PLATE SCREWS. OVERTIGHTENING

SCREWS CAN DAMAGE THE CIRCUIT BREAKER
COVER. USE ONLY HARDWARE PROVIDED, DO
NOT SUBSTITUTE.

2-5.

Secure mounting plate with two special

#10 (4.8

mm)

crossrecessed head, thread-cutting screws

provided. Torque screws to

30

Ib.-in.

(3.5

Nm).

Do not substitute hardware.

2-6.

Move circuit breaker handle to the OFF position.

Hinge lockplate over staple. Check that padlock

shackle fits through staple and that tab on lock

plate blocks path of circuit breaker handle.

2-7.

Remove padlock. Hinge lockplate away from

circuit breaker handle. Move circuit breaker
handle to the

ON

position. Hinge lockplate over

shackle and check that tab blocks path of circuit
breaker handle. (Lock On/Off Styles Only)

Mounting

Plate

Lockplate

Mounting

Plate

Securing

Screws

Staple

Figure 2-2 Mounting Hole Locations

40752-092 (1)

Effective 05/02

Printed in U.S.A. /TQC

Advertising