background image

 Green

 L

 Red

LED Fixed = L pre alarm (0.9 * I1 < I < 1.2 * I1)

LED Blinking =  L alarm (I > 1.2 * I1)

U

 Red

L | U | I

 Red

LED Blinking = Parameters inconsistency - L = I.

LED Blinking without Parameters inconsistency = generic fault (please contact Rockwell Automation)

 LED

 Color

CONDITION  Run time

LED Blinking = U alarm

t6

I6

and

3E

2s<t

i

£3s

5E

3s<ti£5s

@ (7.2 x I1)

10E

5s<ti£10s

20E

10s<ti£20s

In = 100 A
I1 = 100 x (0.4+0.08+0.32)= 80A
CLASS = 3E@(7.2xI1)=2s<t

i

<3s@576A(7.2Ax80)

Esempio:

Example:

I3 =100 x (6+1+2)=900A