Table 1

Gaskets required for various panel thicknesses.
Units are shipped with three 1/16 in. (1.6) gaskets

16 gauge 1/16 in. (1.6)
12 gauge 7/64 in. (2.8)
10 gauge 9/64 in. (3.6)
3/16 in. (4.8)

3 gaskets
2 gaskets
2 gaskets
1 gasket

Panels thicker than 3/16 in. (4.8) must be counterbored to
3/16 In. (4.8) thickness.

NOTE: Dimensions shown in parentheses are in millimeters.

1. Remove lens mounting ring and knob or knob lever assembly.
2. Remove lamp by inserting the lens removal tool onto the lamp, push

down and rotate counter clockwise. Pull out the lamp.

3. Install a new lamp of the correct number. Refer to nameplate for lamp

number. Push lamp into socket using the lamp tool. (Cat. No.: 800E-ALR1)
Rotate clockwise and pull lamp tool out once the lamp is retained.

4. Reinstall the lens assembly by placing the assembly over the shaft.

NOTE: The shaft has a projection which should line up to the knob

indicator. Thread the lens mounting ring onto the bushing once the
knob is seated on the shaft.

An operator may be used with 1 or 2 of the contact blocks listed in Table 2,
except as noted. Multipleblocks must be mounted in tandem and may be in
various combinations, two blocks maximum.

Table 2

Number of Contacts

Standard Block

Cat. No. 800T–

Pen

TUFF

TM

Low Voltage Blocks

Cat. No. 800T–

Logic Reed

Block

Cat. No. 800T–

Sealed Switch Block

Cat. No. 800T–

Stackable Sealed

Switch Blocks

Cat. No. 800T–

1 N.O. – 1 N.C.

XA

800T-XAV

XAR

XAP

800T-XAY

1 N.O.

XD1 AND XD5

800T-XD1V

XD1R

XD1P

800T-XD1Y

1 N.C.

XD2 AND XD6

800T-XD2V

XD2R

XD2P

800T-XD2Y

1 N.O. (Early Make)

XD3

XA2R

1 N.C. (Late Break)

XD4

XA4R

1 N.C. (Late Break) – 1 N.O.

XA1

1 N.C. (Late Break) – 1 N.C.

XA7

2 N.O.

XA2

2 N.C.

XA4

1

1

3

3

4

2 4

4

N.O. = Normally Open

N.C. = Normally Closed

Sealed switch contact blocks may only be mounted singly, directly behind

the operator. (no stacking)

3

Mini contact blocks 800T-XD5 and XD6 may not be mounted directly

behind the operator, stack only on top of another contact block.

4

Hermetically sealed contacts – may be used in Class 1 Division 2
hazardous location applications in an enclosure suitable for the
environment, which need not be a hazardous location enclosure. (Refer to
National Electric Code)

PREFERED METHOD

(4.4)

11/64

(17.1)

43/64

(46.8)

1–27/32

(57.2)

2–1/4

ш
(ш30.6)

1–13/64

ш 1/4 DRILL

(ø6.4)
ALTERNATE METHOD

Minimum
Spacing

Spacing

Figure 2. Hole Recommendation

2

Relamping Instructions

Contact Block Mounting