Iv. conversion module wiring diagram – Rockwell Automation 1492-CM800-LA003 Field Wire Conv. Module for Modicon B872-100 to 1756-OF6CI User Manual

Page 2

Advertising
background image

(2)

10000021838

(Version 00)

IV. Conversion Module Wiring Diagram

The following diagram shows the connections from the existing B872-100 swing-arm, through the conversion module, 1492 cable
and to the 1756-OF6CI analog output module. The diagram can be used as an aid in possible system troubleshooting.

1756-OF6CI

1492-ACABLE003Y

1492-CM800-LA003

Conversion: B872-100 to 1756-OF6CI with 1492-CM800-LA003

B872-100 Swing Arm

Conversion Module Installation and Application Considerations

IMPORTANT: The B872-100 analog output module required the use of an external power supply to drive the analog device. The 1756-OF6CI analog output

provides the drive power to the analog
device. ENSURE the external power supply is REMOVED from the current loop before applying power to the 1756-OF6CI module or the analog output module will
be damaged.

The 1756-OF6CI module can drive a load up to 550 ohms with the standard pre-configured cable [1492-ACABLE003Y]. If greater than 550 ohm drive current is

required, the pre-wired cable can be modified at the 1756-OF6CI terminal block to drive up to 1000 ohms. Refer to the 1756-OF6CI module Installation Manual for
modification details.

SHIELD GROUNDING: The B872-100 analog output module allowed shield grounding at the field device or to the B872-100 “Frame Ground” terminal. The

pre-wired cable used between the 1492-CM800-LA003 and the 1756-OF6CI [1492-ACABLE003Y] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected.

IMPORTANT: The B872-100 analog output module allowed Sinking or Sourcing field wired devices. The 1756-OF6CI analog output provides a Sourcing output

which requires a sinking field device. Please ENSURE the field device is compatible and wired in this fashion before applying power.

The B872-100 analog output module had monitoring terminals to allow for calibration or field monitoring. The 1756-OF6CI does not have such a feature.

Refer to your B872-100 and 1756-OF6CI Installation and User Manuals for additional information concerning comparisons of module wiring, features, and module

configuration details.

[Reference Doc: 41170-780 (Version 03)]

There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation.

WARNING

1492-CM800-LA003 Conversion Module

De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.

WARNING

4

12
11

24
23

31

19
20
21
22
27
28

+
-

3

5

14

7
8

10
15

17
18

26

6

34

9

16

29
30
35
36
37
38
1
2
39

Not Used

Frame Ground

Frame Ground

Current Source 1

13
25
24
23
22
21
19
18
17
16
15
14

SH

12
11
9

6

4
2

20

40

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Monitor 2

Frame Ground

Frame Ground

1

OUT-0
RTN-0

5

OUT-1

2

RTN-1

6

OUT-2

7

RTN-2

11

OUT-3

8

RTN-3

12

RTN-4

19

OUT-4

15

Not Used

14

ALT-3

10

Red
Black

White

Black

Green

Black

Blue

Black

RTN-5

20

OUT-5

16

Yellow

Black

Brown
Black

Orange
Black

Current Source 1

Current Sink 1

13

Current Source 2
Current Source 2

Current Sink 2

25

Current Source 3
Current Source 3

Current Sink 3

33

Current Source 4
Current Source 4

Current Sink 4

32

Monitor 1

Monitor 3
Monitor 4

Advertising