Quick installation guide (continued), Attention, Connecting rod installation – Rockwell Automation 1494V-DSxx Series D Variable Depth Disconnect Switch User Manual
Page 3
Connecting Rod Installation
4
Verify that disconnect switch and handle are in "OFF"
position. (Switch blades will be visible)
Drive Bar
Pull up
(30A - 60A - 100A)
1
2
Rotate connecting rod into
drive bar (see table).
3
4
Enclosure depth
8 in. or less
Enclosure depth
greater than 8 in.
CHECK FOR PROPER
OPERATION
ATTENTION
7
8b
8a
Push rod down and
verify if rod is nearly
touching bottom of bolt
head. (If not, rotate rod
up to 5 full turns in
either direction)
(200A)
Push down
Push rod down and verify if rod
is approximately 1/8" from
touching bottom of bolt head.
(If not, rotate rod up to 5 full
turns in either direction)
1/8" Gap
Switch Rating
30A - 60A - 100A
200A
Full Turns Engagement
10
13
PN-47400
DIR 10000056505 (Version 00)
QUICK INSTALLATION GUIDE (CONTINUED)
(3)
Connecting
Rod
Hitch Pin
Primary Link
5
6
5
6