Communications

Remote Diagnostics and
Remote Bypass

Relay dry contacts are available for remote monitoring of the state of the Bypass
Circuit Breaker CBB and the Input Circuit Breaker CBI shunt-trip condition
(See

Figure 7

). In addition, a customer-supplied relay may be used to remotely

command a Seamless Bypass operation, as described in Publication 1608M-
UM001A-EN-P. These functions are available from terminal block TB1 located
in the upper compartment of the bypass switchboard. See

Figure 9

and

Figure 6

for recommended conduit entry location.

Figure 7 - Schematic Diagram - Status Relay Contacts

CBB Contacts
(Bypass Circuit Breaker)

"Normal" position for the Bypass Breaker is defined as the breaker being OFF, or
Open. As such, the Normally-Open contacts are open when the Breaker is open;
the Normally-Closed contacts will open when the breaker is closed.

Example: Normal run: CBB will be Open; therefore TB1/11B will be electrically
connected to TB1/10B.

K1

5

1

3

6

2

4

7

8

CBB
N/C

CBB1
N/O

TB1

terminal block

NC

1A

C

2A

NO

3A

NC

1B

C

2B

NO

3B

NC

4A

C

5A

NO

6A

NC

4B

C

5B

NO

6B

.

7B

.

8B

.

9B

NC

10B

C

11B

NO

12B

unused

7A

unused

8A

unused

9A

NC

10A

C

11A

NO

12A

NC

13B

C

14B

NO

15B

NC

13A

C

14A

NO

15A

Customer-Supplied Contact:
Close to command
Seamless Bypass