Functional diagram, Front side and user elements, L2 l1 – Rockwell Automation 1606-XLE96B-2 Power Supply Reference Manual User Manual

Page 9: Ab c d

Advertising
background image

All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM030A-EN-P — April 2014

9

Bulletin 1606 Switched Mode Power Supplies

9. Functional Diagram

Fig. 9-1 Functional diagram

+

+

-
-

V

OUT

Output

Over-

Voltage

Protection

PFC

Inductor

Inrush

Limiter

Transient

Filter

Input Fuses

Input Filter

Input
Rectifier

Output

Voltage

Regulator

Power

Converter

Output

Filter

Output

Power

Manager

Temper-

ature

Shut-

down

DC-ok

LED

L2

L1


10. Front Side and User Elements

Fig. 10-1 Front side

A

Output Terminals

Screw terminals, dual terminals per pole

+ Positive output

-

Negative (return) output


B

Input

Terminals

Screw

terminals

L1, L2 Phase input

PE (Protective Earth) input


C

Output voltage potentiometer

Open the flap to set the output voltage. Factory set: 12.0V


D

DC-OK LED (green)

On when the voltage on the output terminals is > 10.5V

A

B

C
D