EN912 - Discrete Input to Output Mapping

Description

Custom Firmware EN912 differs from the standard 1336 PLUS

II

version

3.002 firmware in the following way:

The ability to map (“pass through”) drive discrete inputs from an
optional interface card to digital output relays has been added.
Selections 20-27 have been added to the [CRx Out Select] param-
eters (see below).

Digital Outputs

Digital output parameters are defined as follows:

!

ATTENTION: This Custom Firmware has been designed for a
specific application and differs from the standard 1336 PLUS

II

product offering. It must be installed and run only under this
custom application. Attempting to run this Custom Firmware
under any other type of application or condition could result in
unpredictable and/or hazardous conditions.

[CR1 Out Select]
[CR2 Out Select]
[CR3 Out Select]
[CR4 Out Select]

This parameter sets the condition that changes the state
of the output contacts at TB2 terminals 10 & 11 (CR1), 11
& 12 (CR2), 13, 14, 15 (CR3) and 16, 17, 18 (CR4).

A change of state may mean energize or de-energize the
relay, since some relays may energize on power-up and
de-energize when the selected condition occurs.

A red LED located on the Main Control Board indicates the
status of the CR3 contact. The LED will illuminate when
the contacts at terminals 13 & 14 of TB2 are closed and
terminals 14 & 15 are open.

Parameter Number

158, 174-176

Parameter Type

Read and Write

Factory Default

“At speed” CR1

“Running” CR2

“Fault” CR3

“Alarm” CR4

Units

Display Drive

“Fault” 0

Any fault

“Alarm” 1

Any unmasked alarm

“Running” 2

Outputting frequency

“At Speed” 3

Output = command

“At Freq” 4

Requires value in [Dig Out Freq]

“At Current” 5

Requires value in [Dig Out Curr]

“At Torque” 6

Requires value in [Dig Out Torque]

“Current Lmt” 7

In overload

“Mtr Overload” 8

At present levels O.L. will occur

“Line Loss” 9

Line loss in progress

“Drive Power” 10 Full input volts present, bus charged

“Drive Ready” 11 All necessary commands present

“Forward Run” 12 Forward direction
“Reverse Run” 13 Reverse direction

“Braking” 14 DC brake mode (stopping or holding)

“Economize” 15 Auto economizer active
“Auto Reset” 16 Attempt to reset fault & restart drive

“At Temp” 17 Requires value in [Dig At Temp]

“PI Max Error” 18 Requires value in [PI Max Error]

“Remote” 19 Set by [Remote CR Output]

“Inp.1 TB3-19” 20 Signal present at discrete input 1
“Inp.2 TB3-20” 21 Signal present at discrete input 2
“Inp.3 TB3-22” 22 Signal present at discrete input 3
“Inp.4 TB3-23” 23 Signal present at discrete input 4
“Inp.5 TB3-24” 24 Signal present at discrete input 5
“Inp.6 TB3-26” 25 Signal present at discrete input 6
“Inp.7 TB3-27” 26 Signal present at discrete input 7
“Inp.8 TB3-28” 27 Signal present at discrete input 8