All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

20

Rockwell Automation Publication 1606-RM014A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

21.6. Daisy Chaining of Outputs

Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block.

Fig. 21-3 Daisy chaining of outputs

Fig. 21-4 Using distribution terminals

Power

Supply

+ +

- -

Input

Output

Load

+

-

max 25A!

Power

Supply

+ +

- -

Input

Output

Load

+

-

Distribution

Terminals

Power

Supply

+ +

- -

Input

Output

Power

Supply

+ +

- -

Input

Output

21.7. Inductive and Capacitive Loads

The unit is designed to supply any type of load, including unlimited capacitive and inductive loads.

Advertising