Bulletin 1400
Power Monitoring Products

Instruction Sheet

3

Use the following table to change the default configuration.

8

7

6

5

4

3

2

1

SW1

(1 = On)

not used

set=1

RIO rack address 0–63 (00–77 octal)

8

7

6

5

4

3

2

1

SW2

(1 = On)

not
used
set=1

last
rack
0=no
1=yes

last rack
6 5
0 0=hold
0 1=low
1 0=high
1 1=hold

data rate
4 3
0 0=57.6kBaud
0 1=115kBaud
1 0=230kBaud
1 1=230kBaud

group number
2 1
0 0=group 0
0 1=group 2
1 0=group 4
1 1=group 6

Figure 2
Communications Card Jumper and Switch Locations

J1

RS 485

RS 232

SW2

SW1

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

1. Make sure that all power to the Powermonitor Display/Block Module

is off.

!

ATTENTION: Voltages may still be present when supply power
is turned off to the unit. The unit will generally be powered by
one source and monitoring another source. Turn off or
disconnect all voltages applied to the unit. Failure to do so may
result in personal injury or death.

2. If field retrofitting a Powermonitor Display/Block Module, first remove

the communications port cover plate on the rear cover of the
Powermonitor Display/Block Module.

Reinstalling (or Field
Retrofitting) the
Communications Card