V. 1492-CM800-LA004 Conversion Module Specifications

(Operating specifications are when installed in the Conversion System base / cover-plate assembly)

Specification

Value

Dimensions

288.9 mm (height) x 139.7 mm (depth) x 44.5 mm (width)

11.37 in. (height) x 5.5 in. (depth) x 1.75 in. (width)

Approximate Shipping Weight

300g (0.66 lbs) (includes carton)

Storage Temperature

-40 to +85°C (-40 to +185°F)

Operating Temperature

0 to 55°C (32 to 131°F)

Operating Humidity

5 to 95% at 55°C (non-condensing)

Shock
Non-operating

Operating


50g

30g

Operating Vibration

2g @ 10-500Hz

Maximum Operating Voltage

60 Vdc

Max. Module Operating Current

Per Point:
Per Module:


2 Amps (1492-CABLE connection pins are limited to 2A per pin)

12 Amps

Agency Certifications



UL Classified: Under UL File Number E113724

CSA
CE: compliant for all applicable directives

Pollution Degree

2

Environmental Rating

IP20

Refer to the Wiring Diagram(s) for
current limits for a specific configuration.

NOTICE

6

14
12

26
24

34
32

20
21
22
23
27
28

+
-

4

Analog Output 1

Analog Common 1

5

13

25

3

9
10

15
16

18
19

7

33

8

11

17

29
30
31
35
36
37
38
1
2
39

Not Used

Not Used

Frame Ground

Frame Ground

Analog Common 1

13
25
24
23
22
21
19
18
17
16
15
14

SH

12
11
9

6

4
2

20

1

OUT-0
RTN-0

5

OUT-1

2

RTN-1

6

OUT-2

7

RTN-2

11

OUT-3

8

RTN-3

12

RTN-4

19

OUT-4

15

Not Used

14

Not Used

10

Red
Black

White

Black

Green

Black

Blue

Black

RTN-5

20

OUT-5

16

Yellow

Black

Brown
Black

Orange
Black

Analog Output 2

Analog Common 2
Analog Common 2

Analog Output 3

Analog Common 3
Analog Common 3

Analog Output 4

Analog Common 4
Analog Common 4

40

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Frame Ground

Frame Ground

1492-CM800-LA004 Conversion Module

De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out
to any device in the control cabinet where the conversion is to be performed. Ensure work is performed
by qualified personnel.

WARNING

Advertising