Specification

Dimensions

Approximate Shipping Weight

11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width)
300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)

271.9 g (0.60 lbs) (includes carton)

Storage Temperature

-40 to +85°C (-40 to +185°F)

Operating Temperature

0 to 60°C (32 to 140°F)

Operating Humidity

5 to 95% at 60°C (non-condensing)

Shock

Non

-

operating

Operating

50g

30g

Operating Vibration

2g at 10 to 500Hz (Agrees with 1756 I/O module specifications)

Maximum Operating Voltage

132 Vac at 47 to 63Hz

Max. Module Operating Current

Per Point:

Per Module:

1 Amp
4 Amps

4 Amps

Agency Certifications



UL Classified: Under UL File Number E113724

CSA

CE: compliant for all applicable directives

Pollution Degree

2

Environmental Rating

IP20

Refer to the Wiring Diagram(s) for
current limits for a specific configuration.

NOTICE

Value

Fusing

Sixteen, 1.5 Amps (maximum current based on convension
components)

PN-114282
DIR 10000060093 (Version 01)
Publication 1492-IN040B-EN-E

IV. Conversion Module Specifications

(Operating specifications are when installed in the Conversion System base / cover-plate assembly)

Table 2: Bulletin 1771 to 1756 Conversion Modules and Cables

III. Compatibility

Foot Notes:

To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific 1771

and 1756 I/O modules involved.

The 3 numbers indicate the cable length of each portion of the 1492 Cable. Recommended cable lengths of 0.5M

are shown. Additional cable lengths are as follows:

1.0M = 1492-CONCAB010Y

1771

Digital I/O Module

1756

Digital I/O Module

1492

Conversion Module

1492

Cable

1771-ODD 1756-OA16I 1492-CM1771-LD010F

1492-CONCAB005Y

1771-OQ16

1756-OB16I

1492-CM1771-LD010F

1492-CONCAB005Y

1771-OD16 1756-OA16I

1492-CM1771-LD010F

1492-CONCAB005Y

Advertising