Wiring and Connecting the UPS

C

ONNECTING

UPS

USING POWER CORD

:

3000

VA

U

NITS

1609-P3000N – Use captive 8 ft cord. NEMA L5-30 Plug is attached to this cord.

1609-P3000H – Use in captive 8 ft cord. NEMA L6-30 Plug is attached to this cord.

1609-P3000A – User must supply p ower cord. Power cord must mate with IEC 320 C20 inlet.

H

ARDWIRING

I

NSTRUCTIONS

:

1609-P5000E

Wiring must be performed by a qualified electrician.

Install a high magnetic 30/32 A utility circuit breaker,
(Allen-Bradley Catalog Number 1489-A2C300).

Adhere to all national and local electrical codes.

Use #10 AWG gauge (5 sq. mm) wire.

1. Switch the utility circuit breaker OFF.

2. Remove the input access panel.

3. Remove circular knockout.

4. Run #10 AWG gauge (5 sq. mm) wire through the access panel, and connect the wires to the

terminal block (Green: Ground, Brown: Hot, Blue: Neutral).
Use an appropriate s train relief (not included).

5. Switch the utility circuit breaker ON.

6. Check line voltages.

7. Replace the access panel.