Wiring – Rockwell Automation 1204 Reflected Wave Reduc Device RWR2 User Manual
Page 7
1204 Reflected Wave Reduction Device
7
3. Use the figure below or an actual unit to mark the mounting holes.
Drill and tap the four (4) device mounting holes.
Wiring
4. Wire the device as indicated below. The maximum and minimum
wire size accepted by the RWR2 terminal block is 4.0 and 0.75 mm
2
(10 and 18 AWG). Use Copper wire only with a minimum
temperature rating of 75 degrees C. Maximum torque is 1.81 N-m
(16 lb.-in.).
180 (7.09)
B & C Frames
160 (6.30) – B Frame
200 (7.87) – C Frame
31.8
(1.25)
225.6
(8.88)
Drill & Tap
for
10-32 Screw,
4 Places
Dimensions are in millimeters and (inches)
"Book" Style – B Frame Only
"Stack" Style
U
V
W GRD U1
V1
GRD
W1
Motor Phase U
RWR2 Terminal Block
AC Drive
Motor Phase V
Motor Phase W
Motor Ground
from Drive Terminal W
from Drive Terminal V
from Drive Terminal U
from Drive Ground