1204 Reflected Wave Reduction Device

7

3. Use the figure below or an actual unit to mark the mounting holes.

Drill and tap the four (4) device mounting holes.

Wiring

4. Wire the device as indicated below. The maximum and minimum

wire size accepted by the RWR2 terminal block is 4.0 and 0.75 mm

2

(10 and 18 AWG). Use Copper wire only with a minimum
temperature rating of 75 degrees C. Maximum torque is 1.81 N-m
(16 lb.-in.).

180 (7.09)

B & C Frames

160 (6.30) – B Frame
200 (7.87) – C Frame

31.8

(1.25)

225.6

(8.88)

Drill & Tap

for

10-32 Screw,

4 Places

Dimensions are in millimeters and (inches)

"Book" Style – B Frame Only

"Stack" Style

U

V

W GRD U1

V1

GRD

W1

Motor Phase U

RWR2 Terminal Block

AC Drive

Motor Phase V

Motor Phase W

Motor Ground

from Drive Terminal W

from Drive Terminal V

from Drive Terminal U

from Drive Ground

JOG

ESC

SEL