8 Bulkhead Connections for Series B 1326 Cables

Installing Push-pull and
Bulkhead Connectors

The 1326-xxxT-D-xxx connector has male pins at one end and female
contacts on the other end.

Guidelines for Connecting Cables with Push-pull and Bulkhead
Connectors

These guidelines apply to push-pull and bulkhead cable connections.

• A push-pull connector can connect only to a bulkhead connector or a

460V-1326Ax motor.

• A bulkhead connector can connect only to a push-pull connector.
• One connector must have male pins and the connector it mates with

must have female contacts.

• Cables designated with the L option can connect to cables or motors

without this option, but the resulting connection does not provide the L
option.

• The length of a cable run cannot exceed 90 m (295 ft.).

WARNING

All series B cable connectors are treated with a black,
highly-conductive, cobalt coating. Do not scrape this coating.