Iv. conversion module wiring diagram, Module a module b – Rockwell Automation 1492-CM800-LD012 Field Wire Conv. Module for Modicon B838-032 to Two 1756-OB16E User Manual

Page 2

Advertising
background image

(2)

10000021903

(Version 00)

IV. Conversion Module Wiring Diagram

The following diagram shows the connections from the existing B838-032 swing-arm, through the conversion module, two 1492
cables and to the two 1756-OB16E output modules. The diagram can be used as an aid in possible system troubleshooting.

1756-OB16E

1756-OB16E

1492-CABLE003X

1492-CABLE003X

1492-CM800-LD012

Conversion: B838-032 to 1756-OB16E Qty 2 with 1492-CM800-LD012

B838-032 Swing Arm

Conversion Module Installation and Application Considerations

This configuration uses two (2) 1756-OB16E output modules to replace a single B838-032 output module. This may require

the use of a larger 1756 I/O Chassis. Ensure there is sufficient panel space to allow for this possibility.

The B838-032 module output current limits versus 1756-OB16E limits are as follows:

B838-032

1756-OB16E w/ 1492-CABLE003X

a) Current/Point

0.5A

1A

b) Current/Group

----

2A

c) Current/Module

16A (32 pts)

4A (16 pts)

d) Surge Current/Pt

2.5A for 0.5ms

2A for 10ms

The B838-032 module provided a single mechanical fuse per group. The 1756-OB16E is electronically fused per group.

Refer to the 1756-OB16E Installation Manual for electronic fusing details.

The 1492-CABLE003X current is limited to 2A per pin.

 Refer to your B838-032 and 1756-OB16E Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded.

[Reference Doc: 41170-762 (Version 03)]

1
2
3
4

1

5

21

6

2

7

22

8

3

9

23

10

4

11

24

12

7

13

27

8

15

28

16

9

17

29

18

10

19

30

20

14

11

31

12

32

13

33

14

34

17

37

18

38

19

39

20

40

26

16

Output 1

Output 17

Output 2

Output 18

Output 3

Output 19

Output 4

Output 20

Output 5

Output 21

Output 6

Output 22

Output 7

Output 23

Output 8

Output 24

Output 9

Output 25

Output 10

Output 26

Output 11

Output 27

Output 12

Output 28

Output 13

Output 29

Output 14

Output 30

Output 15

Output 31

Output 16

Output 32

36

5
6

Group 1(-)

+

-

LOAD

25

15

35

Group 3(-)

Group 2(-)

Group 4(-)

Group 1(+)

Group 3(+)

Group 2(+)

Group 4(+)

10

DC-0+

OUT-0

1

OUT-1

2

OUT-2

3

OUT-3

4

OUT-4

5

OUT-5

6

OUT-6

7

OUT-7

8

OUT-8

11

OUT-9

12

OUT-10

13

OUT-11

14

OUT-12

15

OUT-13

16

OUT-14

17

OUT-15

18

Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green

DC-1+

20

9

RTN OUT-0

19

RTN OUT-1

1
2
3
4
5
6
7
8
9
10
11
12
13

15
16
17
18
19
20

14

10

DC-0+

OUT-0

1

OUT-1

2

OUT-2

3

OUT-3

4

OUT-4

5

OUT-5

6

OUT-6

7

OUT-7

8

OUT-8

11

OUT-9

12

OUT-10

13

OUT-11

14

OUT-12

15

OUT-13

16

OUT-14

17

OUT-15

18

Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green

DC-1+

20

9

RTN OUT-0

19

RTN OUT-1

MODULE

A

MODULE B

P1

P2

There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation.

WARNING