Rockwell Automation 1329I ACDrive/Motor SerA Quick Ref User Manual

Page 2

Advertising
background image

PE

DC+

DC-

DBR

T/L3

S/L2

R/L1

DC Bus (Do Not Wire)

DBR (Do Not Wire)

AC Inputs

AC Input Power Connections

1

2

34

5678

9

1

0
11
1

2
1

3
1

4
1

5
1

6
1

7
1

8
1

9
2

0

10 Volt Reference

0 – 10V DC Speed Reference Input

4 – 20 mA Speed Reference Input

Common

0 – 10 Volt Output

Common

Speed Preset 2

Speed Preset 1

Speed Preset 0

Forward/Reverse

24 Volt DC

RPM/Percent Load Display

Reset

Start

Stop

24 Volt DC Common

N.O. Relay

Relay Common

24 Volt DC

Function Loss

-

+

RPM

% Load

OFF ON

Enabled

Terminal Block

Faulted

Enabled

Constant

Ramp-to-Rest

Disabled

From Terminal Block

Run On Power Up

Speed Reference

Relay Control Output

Auto Restart

Torque Curve

Stop

Reverse

Minimum Speed

Not Used

Not Used

Disabled

Operator Controls

Running

Disabled

Variable

Coast-to-Rest

Enabled

3 Hz

Setup DIP Switch (SW3)

Switch 2 applies to local operator control units only.

1

2

34

5678

9

1

0
11
1

2
1

3
1

4
1

5
1

6
1

7
1

8
1

9
2

0

10 Volt Reference

0 – 10V DC Speed Reference Input

4 – 20 mA Speed Reference Input

Common

0 – 10 Volt Output

Common

Speed Preset 2

Speed Preset 1

Speed Preset 0

Forward/Reverse

24 Volt DC

RPM/Percent Load Display

Reset

Start

Stop

24 Volt DC Common

N.O. Relay

Relay Common

24 Volt DC

Function Loss

-

+

+10V DC

5K

RPM

Fwd

Rev

% Load

13

16

17

Maintained 2-Wire Start.

Momentary 3-Wire Start.

0 = 1 Second Accel/5 Sec Decel
1 = 5 Seconds (Default)
2 = 10 Seconds
3 = 15 Seconds
4 = 20 Seconds
5 = 30 Seconds
6 = 60 Seconds
7 = 90 Seconds

0 = 1500 RPM (50 Hz)
1 = 1800 RPM (60 Hz) Default
2 = 2100 RPM (70 Hz)
3 = 2400 RPM (80 Hz)
4 = 2700 RPM (90 Hz)
5 = 3000 RPM (100 Hz)
6 = 3300 RPM (110 Hz)
7 = 3600 RPM (120 Hz)

Max Speed Switch (SW2)

Accel/Decel Switch (SW1)

ATTENTION: All adjustments to these components
should be made with the power removed. Failure to
observe this precaution could result in severe bodily
injury or loss of life.

ATTENTION: After disconnecting input power, wait
five minutes and check with voltmeter to assure that
DC bus capacitors are discharged (DC+, DC-).
The voltmeter should read zero volts.

Control Signal Terminal Block

ATTENTION: The cover screws must be securely
tightened in order to properly ground the cover.
Verify that all four cover screws are tight before
applying power to the unit. Failure to observe this
precaution may result in severe bodily injury or loss
of life.

Standard Unit

Local Operator Control Unit

Connect to external device.

The jumber between terminals 7 and 11 must be removed when wiring the Function Loss input.
See Section 7.1 of the User Manual for more information.

An external 0 to 10 volt or 4 to 20 mA speed reference source can be connected.
See Section 7.5.3 of the User Manual for more information.

= N.O. Momentary Contact

= N.C. Momentary Contact

= Maintained Contact - Closed

= Maintained Contact - Open

Ground

= Default Setting (OFF Position)

Connect to external device.