Environment – Rockwell Automation 1606-XLSBUFFER48 Power Supply Reference Manual User Manual

Page 9

Advertising
background image

All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM027A-EN-P — April 2014

9

Bulletin 1606 Switched Mode Power Supplies

14. EMC

The unit is suitable for applications in industrial environnent as well as in residential, commercial and light industry
environments without any restriction. The CE Mark is in conformance with EMC guidelines 89/336/EEC and 93/68/EEC and
the low-voltage directive (LVD) 73/23/EWG.
A detailed EMC Report is available on request

EMC Immunity

EN 61000-6-1 EN 61000-6-2

Generic standards

Electrostatic discharge 1)

EN 61000-4-2

Contact discharge
Air discharge

8kV
15kV

Criterion A
Criterion A

Electromagnetic RF field

EN 61000-4-3 80MHz-1GHz

10V/m

Criterion

A

Fast transients (Burst)

EN

61000-4-4

2kV Criterion

A

Surge voltage

EN 61000-4-5

+ -
+ / - housing

500V
500V

Criterion A
Criterion A

Conducted disturbance

EN 61000-4-6

0,15-80MHz

10V

Criterion A

1)

Grounded on the DIN rail

EMC Emission

EN 61000-6-3 and EN 61000-6-4

Generic standards

Conducted emission

EN 55022

Class B

Radiated emission

EN 55011, EN 55022

Class B

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

15. Environment

Operational temperature

-25°C to +70°C

full power

Storage temperature

-40 to +

85°C

storage and transportation

Humidity

5 to 95% r.H.

no condensation allowed

Vibration sinusoidal

2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g

IEC 60068-2-6

Vibration random

0.5m

2

(s

3

)

IEC 60068-2-64

Shock

30g 6ms, 20g 11ms

IEC 60068-2-27

Altitude

0 to 6000m

All approvals apply only up to 2000m

Over-voltage category

III

EN 50178

II

EN 50178 above 2000m altitude

Degree of pollution

2

EN 50178, not conductive

The ambient temperature is defined 2cm below the unit.