Preparing low voltage door for 85 plus – Rockwell Automation 1500 Modular Protection System Conversion Kit (GE Multilin to Bulletin 825 Plus) User Manual

Page 18

Advertising
background image

1500-IN059C-EN-E – June 2013

4-4

Installation

Preparing Low Voltage Door

for 85 Plus

1. Once the door has been removed, place the door on a level work

surface.

2. Position an 825 Plus Mounting Collar squarely on the low voltage

door to align with the existing GE Multilin relay mounting notes.

(Figure 4.5)

3. Using the collar as a template, lightly trace the cutout area on the

inside and outside of the collar. This outline represents the minimum

and maximum size required by the 825 Plus relay. (Figure 4.6)

4. Double-check the measurements before cutting. With a cutting tool,

cut on the outside edge of the inside cutout trace. (Figure 4.7)

5. To ensure the hole is of the correct size, place a mounting collar over

the hole. There should be no metal showing on the inside of the collar,

and the collar should not pass through the cutout. (Figures 4.8 and

4.9)

Remove all metal-chips and splinters before mounting

the 825 Plus relay.

Failure to remove all metal chips and splinters can result

in equipment damage or hazardous operation.

Figure 4.5

Figure 4.6

Figure 4.7

Figure 4.8

Figure 4.9

ATTENTION

IMPORTANT