Rockwell Automation 1503FR MV Controllers - Adjustment to Interlocking Mechanism User Manual

Page 9

Advertising
background image

Product Description

2-3

1503FR-IN001B-EN-E – June 2013

Figure 2.3 – Interlock Cam

4) Manually move the top mounted interlock lever so

the top mounted contactor is in the closed position.
The gap between the interlock cam and the interlock
lever should be between .031” and .052”.

Note:
Use a ¼” flat washer as required to space
interlock lever and cam to obtain a proper
clearance. (Figure 2.4)














5) Secure the 5/16” Adjustment Nut, shown in

figure 2-2, to maintain the distance range

established from the prior step.


6) Release the top mounted interlock lever so the

top mount contact is in the open position. The

gap between the interlock cam and the

interlock lever should be between. 031” and

.052”.


Figure 2.4 – Clearance Between Interlock Lever: Contactor Closed

Advertising