Rockwell Automation 1485 PowerTap Connection User Manual

Page 2

Advertising
background image

Publication 75006–280–01(B)

September 2000

Printed in USA

Visit our web site at:

http://www.ab.com/sensors

Figure 3: Cable Stripping Installation for PowerTap Connection

5/16

A

Cable Jacket

Dimension A"

Trunk Cable

4 inches

Trunk Cable

4 inches

Figure 4:

Loosened

Gland Nut

Tightened

Gland Nut

Align Wire End with Clamping

Cavity of Terminal Block

Gland Nut

Hex Flange

Locking Nut

End of Cable Jacket Should

Protrude Approx. 1/8 in.

Input from

Power Supply

1. To install trunk cable into PowerTap connection cut and

strip gray PVC cable back approximately 4 inches (see
Figure 3) and insert through large cable gland. Note:
Trunk cable used for input from power supply should have
white and blue leads cut off short.

2. Loosen gland nut and insert cable until approximately 1/8

inch of cable jacket protrudes.

3. Firmly tighten gland nut to provide strain relief and sealing.

Caution: The hex flange must be held with the cable gland
wrench during tightening.

4. Bare wire ends should be firmly twisted to eliminate loose

strands and each lead looped approximately as shown, to
allow insertion into the clamping cavity of the terminal
block. (See Figure 2 for color codes.)

ATTENTION: Be certain to use insulating tubing
(included in accessory kit) on bare drain wire.

5. To attach cable to terminal strips, press down on cage

clamp, insert wire and release cage clamp. Repeat
process for remaining wires.

6. After all cables are terminated, the cover should be

installed and securely tightened to ensure washdown
rating.

All external wiring must conform to national electric code and
local codes.

Advertising