Worldwide representation – Rockwell Automation 1336R REGEN Sync Cable Repl. User Manual

Page 2

Advertising
background image

Rockwell Automation helps its customers receive a superior return on their investment by bringing
together leading brands in industrial automation, creating a broad spectrum of easy-to-integrate
products. These are supported by local technical resources available worldwide, a global network
of system solutions providers, and the advanced technology resources of Rockwell.

Worldwide representation.

Argentina • Australia • Austria • Bahrain • Belgium • Bolivia • Brazil • Bulgaria • Canada • Chile • China, People’s Republic of • Colombia • Costa Rica • Croatia • Cyprus
Czech Republic • Denmark • Dominican Republic • Ecuador • Egypt • El Salvador • Finland • France • Germany • Ghana • Greece • Guatemala • Honduras • Hong Kong
Hungary • Iceland • India • Indonesia • Iran • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Macau • Malaysia • Malta • Mexico
Morocco • The Netherlands • New Zealand • Nigeria • Norway • Oman • Pakistan • Panama • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia
Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic of • Spain • Sweden • Switzerland • Taiwan • Thailand • Trinidad • Tunisia • Turkey • United Arab Emirates
United Kingdom • United States • Uruguay • Venezuela

Rockwell Automation Headquarters, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414 382-2000, Fax: (1) 414 382-4444

Publication 1336 REGEN-5.12 — May, 1998

P/N 189810 (01)

Copyright 1998 Rockwell International Corporation Printed in USA

PRECHARGE BOARD

CONNECTOR J1

ESC

SEL

CONTROL BOARD

CONNECTOR J13

CONTROL BOARD
CONNECTOR J14

J1

1336 REGEN PRECHARGE UNIT

1336 REGEN CONVERTER

J13

J14

2 OR 4 METER

INTERCONNECTING

SYNC CABLE

1.

Remove and lock-out all incoming power to the 1336 REGEN Line Regeneration
Package.

a.

Remove the Precharge Unit front cover. Measure the voltage at input power
terminals R1–S1–T1 and terminal block TB1 with a voltmeter to ensure that
no voltage is present.

b.

Remove the Converter front cover. Measure the voltage at input power terminals
R2–S2–T2 with a voltmeter to ensure that no voltage is present.

2.

Install the new Precharge-to-Converter Interconnecting Sync Cable in place of the
old, maintaining the same routing, and connect as shown.

!

ATTENTION:

Replace any guards or shields previously removed before

reapplying power to the 1336 REGEN Line Regeneration Package. Failure
to replace guards or shields may result in death or serious injury.