Specifications – Rockwell Automation 1414-ITXxxxxx_CTXxxxxx Duct Average Temperature Transmitter User Manual

Page 5

Advertising
background image

Duct Average-temperature Transmitter 5

Publication 1414-IN004B-EN-P - July 2010

Specifications

Technical Specifications - Duct Average-temperature Transmitter

Attribute

1414-ITX03ACDAA, 1414-ITX02ACDAA,
1414-CTQ03AIEAA, 1414-CTX03PCDAA

Standard lengths

20 ft

Operating temperature range

0…70 °C (32…158 °F)

Probe type

Flexible copper tube

Wiring connections

Terminal blocks

Enclosures

Plastic ABS - UL94-V - NEMA 1
Aluminum - NEMA 3R

Sensor type

1 K

Ω Platinum RTD

Commercial and Hybrid: ±0.3%
Class B Industrial: ±0.2% Class A

Cable

FT-6 plenum rated cable

Probe

304 Stainless steel straight tip, 6.35 mm (0.25 in.) OD
Bendable soft copper tubing, 7.94 mm (0.3125 in.) OD

Output signal

4…20 mA current loop

Transmitter accuracy

±0.1% of span, including linearity

Power supply

15…35V DC

Consumption

Current: 22.5 mA Max. (with open sensor)

PCB operating temperature

0…70 °C (32…158 °F)

Wiring connection

Screw terminal block (14…22 AWG)

TIP

Duct Temperature Averaging has four sensors on < 20 ft probe length and nine
sensors on 24 ft probe length. A rigid, straight, stainless-steel probe is used on
lengths shorter than 36 in.