Specifications – Rockwell Automation 1414-ITXxxxxx_CTXxxxxx Duct Average Temperature Transmitter User Manual
Page 5
Duct Average-temperature Transmitter 5
Publication 1414-IN004B-EN-P - July 2010
Specifications
Technical Specifications - Duct Average-temperature Transmitter
Attribute
1414-ITX03ACDAA, 1414-ITX02ACDAA,
1414-CTQ03AIEAA, 1414-CTX03PCDAA
Standard lengths
20 ft
Operating temperature range
0…70 °C (32…158 °F)
Probe type
Flexible copper tube
Wiring connections
Terminal blocks
Enclosures
Plastic ABS - UL94-V - NEMA 1
Aluminum - NEMA 3R
Sensor type
1 K
Ω Platinum RTD
Commercial and Hybrid: ±0.3%
Class B Industrial: ±0.2% Class A
Cable
FT-6 plenum rated cable
Probe
304 Stainless steel straight tip, 6.35 mm (0.25 in.) OD
Bendable soft copper tubing, 7.94 mm (0.3125 in.) OD
Output signal
4…20 mA current loop
Transmitter accuracy
±0.1% of span, including linearity
Power supply
15…35V DC
Consumption
Current: 22.5 mA Max. (with open sensor)
PCB operating temperature
0…70 °C (32…158 °F)
Wiring connection
Screw terminal block (14…22 AWG)
TIP
Duct Temperature Averaging has four sensors on < 20 ft probe length and nine
sensors on 24 ft probe length. A rigid, straight, stainless-steel probe is used on
lengths shorter than 36 in.