Rockwell Automation 1608P ProDySC Installation Instructions, 25 and 50 A User Manual

Page 13

Advertising
background image

Rockwell Automation Publication 1608P-IN001B-EN-P - May 2014

13

Installation

Chapter 2

Table 2 - ProDySC 25 Amp Power Cable Terminations

Table 3 - ProDySC 50Amp Power Cable Terminations

3 Wire with a Ground

Terminal

Connection

Function

Terminal Marking

Wire Range

AWG (mm2)

Torque lb-in

(Nm)

AC Input

Phase A, B, C

L1, L2, L3

24- 8 (0.5-6)

7.1- 8.9
(0.8-1)

Ground

¼-20 Stud

65
(7.3)

AC Output

Phase A, B, C

X1, X2, X3

24-8 (0.5-6)

7.1- 8.9
(0.8-1)

Ground

¼-20 Stud

65
(7.3)

4 Wire with a Ground

AC Input

Phase A, B, C

L1, L2, L3

24- 8 (0.5-6)

7.1- 8.9
(0.8-1)

Ground

¼-20 Stud

65
(7.3)

Neutral

N

10-0 (6-50)

24.9- 26.7
(2.8-3)

AC Output

Phase A, B, C

X1, X2, X3

24- 8 (0.5-6)

7.1- 8.9
(0.8-1)

Neutral

N

10-0 (6-50)

24.9- 26.7
(2.8-3)

Ground

¼-20 Stud

65
(7.3)

3 Wire with a Ground

Terminal

Connection

Function

Terminal Marking

Wire Range

AWG (mm2)

Torque lb-in

(Nm)

AC Input

Phase A, B, C

L1, L2, L3

10-0 (6-50)

24.9-26.7
(2.8-3)

Ground

¼-20 Stud

65 (7.3)

AC Output

Phase A, B, C,

X1, X2, X3

10-0 (6-50)

24.9-26.7
(2.8-3)

Ground

¼-20 Stud

65 (7.3)

4 Wire with a Ground

AC Input

Phase A, B, C
and Neutral

L1, L2, L3, N

10-0 (6-50)

24.9-26.7
(2.8-3)

Ground

¼-20 Stud

65 (7.3)

AC Output

Phase A, B, C
and Neutral

X1, X2, X3, N

10-0 (6-50)

24.9-26.7
(2.8-3)

Ground

¼-20 Stud

65 (7.3)

WARNING: The ProDySC must be safety-grounded according to the National
Code. In addition, all local, state, and federal regulations applicable to the
installation of electrical systems as well as accident prevention regulations
must be strictly observed.

Advertising