Floor mounting, Bypass switch – Rockwell Automation 1608P ProDySC User Manual, 100/110 A User Manual
Page 8
8
Rockwell Automation Publication 1608P-IN002B-EN-P - May 2014
Chapter 2
Installation
Floor Mounting
The ProDySC is to be secured to the floor using 3/8” hardware and fittings
appropriate for the type of floor. Holes are provided in the base channels; see
Figure 1
for mounting dimensions.
Note: Top or bottom cable entry is allowed. See
Figure 1
and
Figure 4 on page 10
.
Figure 1 - Bottom View Floor Mount Dimensions
Bypass Switch
Installation of the ProDySC with an external maintenance bypass switch is
required for service and/or maintenance. Mount the bypass switch adjacent to
the ProDySC if possible.
The recommended Bulletin 1608P bypass switch has three modes of operation
and is configured as shown in
Figure 2
.
Figure 2 - Bypass switch and mode operation
NORMAL Mode -
Power flows from the utility source
through the ProDySC to the load.
TEST Mode -
Power flows directly from the utility to
the load. ProDySC outputs are not connected to the
load. ProDySC inputs have power provided for testing
by a qualified technician.
BYPASS Mode -
Power flows directly from the utility
to the load. No power is present on ProDySC inputs or outputs.