6

8

1006259

1

2

3

Connecting

Rod

Min.

Max.

"N"

Standard

Extended

Catalog Number

1494V-RB1

1494V-RB2

9"

9-1/4"

9"

23"

Connecting Rod Installation

Right Hand Operation

Connecting Rod Adjustment Procedure

N

Enclosure

Working Depth

(Flange to

Mounting Plate)

N - 3"

Front

Connecting

Link

a) Install connecting rod into the support rod bracket and
thread in clockwise (5) full turns
b) Install connecting rod into the drive bar mechanism
and thread in clockwise (9) full turns

a) Place the disconnect handle in the "OFF" position. Attach
the end of the connecting rod to the primary link of the handle
with two 1/4-20 x 1/2" slotted head screw assemblies and
tighten to 40 lb-in torque.
b) Attach the second connecting rod to the top of the spring
bracket with two 1/4-20 x 1/2" slotted head screw assemblies
and tighten to 40 lb-in torque.
c) Attach the two springs to the mechanism as shown below:

4

5

"ON" Position

a) Move disconnect handle to the "ON" position.

b) If switch does not fully close, return handle to "OFF"
position.

c) Loosen and remove the two 1/4-20 slotted hex head screw
assemblies that hold the connecting rod to the connecting link.

d) Turn connecting rod counter-clockwise (1) full turn.

e) Re-assemble the two 1/4-20 hex head assemblies and
tighten to 40 lb-in and re-test.

f) Repeat 4a - 4e as necessary.

"OFF" Position

g) Move disconnect handle to the "OFF" position.

h) If switch does not fully open, return handle to "ON" position.

j) Loosen and remove the two 1/4-20 slotted hex head screw
assemblies that hold the connecting rod to the connecting link.

k) Turn connecting rod clockwise (1) full turn.

l) Re-assemble the two 1/4-20 hex head assemblies and tighten
to 40 lb-in and re-test.

m) Repeat 5g - 5l as necessary.

(6)

Spring
Bracket

Support Rod
Bracket

Drive Mechanism