V. wiring diagrams (cont’d), Cable”b, Cable”a – Rockwell Automation 1492-CM1771-LA003 Analog & Digital I/O Conversion Module User Manual

Page 7

Advertising
background image

(7)

V. Wiring Diagrams (Cont’d)

There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

WARNING

1771-WC Swing Arm
From 1771-OG

1771-WC Swing Arm
From 1771-OG

Conversion Module

1492-CM1771-LA003

Conversion Module

1492-CM1771-LA003

Cable

1492-C005005XS

1756-OG16

Conversion: 1771-OG (2) to 1756-OG16 (1)

Output
Device

13
25
24
23
22
21
19
18
17
16
1
2

SH

Output 0

+ DC

10

OUT-0
OUT-1

1

OUT-2

2
3
4
5
6
7

9

8

Red/White

Green/Black/White

Black/White/Red

White/Black/Red

Orange/Green

Red/Black/White

Orange/Red

Blue/Red

+
-

A

3
4
5
6
7
B

0
1
2

Common

Output 1

Output 2
Output 3
Output 4
Output 5
Output 6
Output 7

3
4
5
6
7
8
9
10
11
12
14
15

20

OUT-3
OUT-4
OUT-5
OUT-6
OUT-7

+ DC -0

- DC -0

20

OUT-8
OUT-9
OUT-10
OUT-11
OUT-12
OUT-13
OUT-14
OUT-15

+ DC -1

- DC -1

13
25
24
23
22
21
19
18
17
16
1
2

SH

Red/White

Green/Black/White

Black/White/Red

White/Black/Red

Orange/Green

Red/Black/White

Orange/Red

Blue/Red

A

3
4
5
6
7
B

0
1
2

3
4
5
6
7
8
9
10
11
12
14
15

20

Output 8

+ DC

Common

Output 9

Output 10
Output 11
Output 12
Output 13
Output 14
Output 15

11
12
13
14
15
16
17
18
19

Black/Red

White/Red

Black/Red

White/Red

CABLE”B”

+

-

5V DC

SUPPLY

Output
Device

+
-

+

-

5V DC

SUPPLY

Conversion Module Installation and Application Considerations

This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OG16 RTB. Each cable can be either 0.5M or

1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.

The input delay times for the 1771-OG module versus the 1756-OG16 module are as follows:

1771-OG

1756-OG16 w/ 1492-C005005XS

a) Off-to-On Delay

1ms (+/-10ms)

45ms max (plus selectable filter)

b) On-to-Off Delay

1ms (+/-10ms)

145ms max (plus selectable filter)

The 1771-OG module is rated 5V DC TTL INPUT MODULE. The 1756-OG16 module is rated 5V DC TTL INPUT MODULE only.

Refer to your 1771-OG and 1756-OG16 Installation and User Manuals for additional information concerning comparisons of module wiring,

features and configuration details.

[Reference Doc: 41171-028 (Version 00)]

PN-114289
DIR 10000060100 (Version 01)
Publication 1492-IN047B-EN-E

CABLE”A”

Advertising