IV. Conversion Module Wiring Diagram (Continued)

Conversion Module Installation and Application Considerations

The voltage range of the B820-008 module is 10-60VDC and the 1756-OC8 is 30-60VDC. If the load source voltage is

less than 30VDC range, use the 1756-OB8.

The B820-008 module output current limits versus 1756-OC8 limits are as follows:

B820-008

1756-OC8 w/ 1492-CABLE003U

a) Current/Point

2A

2A

b) Current/Group

6A

- -

c) Current/Module

12A

8A

d) Surge Current/Pt

10A for 10ms

4A for 10ms

The B820-008 has 4 groups (allowing 4 separate power supplies) and the 1756-OC8 has 2 groups. This module/cable

combination ties Groups 1 & 2 from the B820-008 to Group 0 on the 1756-OC8 and it ties Groups 3 & 4 from the B820-008
to Group 1 on the 1756-OC8. Field wiring modification must be made to accommodate this if multiple supplies were used.
If 4 supplies were used, 2 must be removed.

The B820-008 provided a single fuse per group. The 1756-OC8 is NOT fused. The 1492-CM800-LD006 provides a

5x20mm fuse per 1756-OC8 Group. Fuse rating for this configuration is 4 Amps.

The 1492-CABLE003U current is limited to 2A per pin.

Refer to your B820-008 and 1756-OC8 Installation Manual wiring schematics and diagrams.

Ensure 1756 output

module ratings are not exceeded.

[Reference Doc: 41170-768 (Version 03)]

1756-OC8

1492-CABLE003U

1492-CM800-LD006

Conversion: B820-008 to 1756-OC8 with 1492-CM800-LD006

B820-008 Swing Arm

1

1

2

2

3

7

4

8

5
6
7

4

8
9

10

10
11
12

14

13

20
11

15

12

16

17

17

18

18
19
20

14

Output 1

Output 3

Output 2

Output 4

LOAD

Supply Voltage Grp 1

Output 5

Output 7

Output 6

Output 8

3

Common Grp 1

9

Common Grp 2

13

Common Grp 3

19

Common Grp 4

5

Not Used

6
15
16

Not Used

Not Used

Not Used

Supply Voltage Grp 2

Supply Voltage Grp 3

Supply Voltage Grp 4

+

-

2

DC-0(+)
OUT-0

3

OUT-1

5

OUT-2

7

OUT-3

9

OUT-4

4

OUT-5

6

OUT-6

8

OUT-7

10
12
14
16
18
11
13
15
17

RTN OUT-1

19

1

RTN OUT-0

20

RTN OUT-1

DC-0(+)
DC-0(+)
DC-0(+)
RTN OUT-0
DC-1(+)
DC-1(+)
DC-1(+)
DC-1(+)

Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green

There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation. In addition, refer to the current draw requirements of the existing
loads for this configuration to ensure they are within the current ratings of the 1756 output module.

WARNING