3. Calibrate the unit in the field by using precision resistance values equal to the zero and

span of the temperature range.

4. Replace the attached probe with the resistor, then adjust the ZERO and SPAN pots

accordingly to obtain the correct output signal.

5. Repeat the adjustments until both values are correct.

Wiring Digram

4…20 mA loop signal

NEG
SEN
EXC

PW

R

OUT

COM

SPAN

ZERO

CONTROLLER

24V DC

IN

PT1000 ohm

Temp Sensor

Sinking 4…20 mA signal w/excitation from controller

4…20 mA loop signal

NEG
SEN
EXC

PW

R

OUT

COM

SPAN

ZERO

CONTROLLER

IN

PT1000 ohm

Temp Sensor

Power Supply

24V DC

( - )

( + )

COM

4…20 mA signal w/external 24V DC power supply