All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM010A-EN-P — February 2014

17

Bulletin 1606 Switched Mode Power Supplies

17.6. Mounting Orientations

Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:

Curve A1 Recommended

output

current.

Curve A2

Max allowed output current (results in approximately half the lifetime expectancy of A1).

Fig. 17-3
Mounting
Orientation A
(Standard
orientation)

Redundancy

Module

INPUT

OUTPUT

Output Current

0

20

30

40

50

70°C

10

20

30

40A

60

A1

Ambient Temperature

Fig. 17-4
Mounting
Orientation B
(Upside down)

Redundancy

Module

INPUT

OUTPU

T

Output Current

0

20

30

40

50

70°C

10

20

30

40A

60

A1

Ambient Temperature

Fig. 17-5
Mounting
Orientation C
(Table-top
mounting)

Output Current

0

20

30

40

50

70°C

10

30

40A

60

20

A1

A2

Ambient Temperature

Fig. 17-6
Mounting
Orientation D
(Horizontal cw)

Redundancy

Module

INPUT

OUTPUT

Output Current

0

20

30

40

50

70°C

10

30

40A

60

20

A1

A2

Ambient Temperature

Fig. 17-7
Mounting
Orientation E
(Horizontal ccw)

Redundancy

Module

IN

PUT

OUTPUT

Output Current

0

20

30

40

50

70°C

10

30

40A

60

20

A1

A2

Ambient Temperature