WARNING: Explosion Hazard.

Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.

This equipment is suitable for use in Class I, Division 2, Groups A,B,C and D or non-hazardous locations only.

Substitution of components may impair

suitability for Class I, Division 2. Power, input and output (I/O) wiring must be in accordance with Class I, Div. 2 wiring methods - Article 501 - 10 (B) (1)
of the National Electrical Code.

PN-90363
DIR 10000135242 (Version 01)
Publication 1492-IN103B-MU-E

(5)

Relay Contact Rating
Spécification du Contact à Relais

700-TBS24

Relaiskontakt-Nennwerte
Classificazione Contatti di Relay

Capacidad Nominal del Contacto de Relé

Maximum Module Current

·

0.75 Amp per relay output

Replacement Relays

·

24VDC Control Voltage: 700-TBS24

Electrical Ratings
ORDINARY LOCATIONS
HAZARDOUS LOCATION

0.75 A DC Ta 0°C - 40°C
0.5 A DC Ta 0°C - 50°C

Output

Rated Insulation Voltage (Ui )

250V IEC, 300V UL/CSA

1-Pole, 1 N.O. 1A

Rated Thermal Current (I th )

Load Voltage Range

0...24VDC

max. 100μA (@U=24V)

33 V

Max. Switching Current

Max. Repetitive Blocking Voltage

On State Voltage Drop @ Max.
Switching Current

< 120mVDC

Leakage Current

Ind. Cont. Eq. for Haz. Loc.
Listed A196
Class I, Div.2, Groups A,B,C,D
Class I, Zn2, Groups IIC

Listed Ind. Cont. Eq. A191