CIRCUIT BREAKER AND ACCESSORY

INSTALLATION INSTRUCTION SHEET

1

1013923

42052-074

OF

N/A

N/A

N/A

REVISION

AUTHORIZATION

DR.

CHKD.

APPD.

DATE

DATE

DATE

E - DOC

LOCATION: MILWAUKEE, WISCONSIN U.S.A.

B-vertical.ai

DWG.

SIZE

SHEET

B

1

2

3

4

5

6

7

8

A

B

C

D

E

F

G

H

REFERENCE

DIMENSIONS APPLY BEFORE

SURFACE TREATMENT

(DIMENSIONS IN INCHES)

TOLERANCES UNLESS

OTHERWISE SPECIFIED

.XX:

.XXX:

ANGLES:

42052

THIS DRAWING IS THE PROPERTY OF

ROCKWELL INTERNATIONAL CORPORATION

OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,

USED OR DISCLOSED FOR ANY PURPOSE

EXCEPT AS AUTHORIZED IN WRITING BY

ROCKWELL INTERNATIONAL CORPORATION

---------------

---------------
---------------

---------------

---------------

---------------

6

7

Auxiliary Installation

Testing of Auxiliary Contacts

1.

Move the disconnect handle on the combination starter to the OFF position.

2.

Fasten the cam and bushings to the bail with (2) flat washers, (2) lock washers, and (2) screws Tighten to 12 - 16 lb-in.

3.

Fasten the base assembly to the support bracket with (2) screws. Tighten to 7 - 10 lb-in.

4.

Attach the assembly from Step 3 to the ear on the support plate with (2) screws. Tighten to 7 - 10 lb-in.

5.

Attach the auxiliary contact with the safety guard to the base assembly.

Note:

If a single auxiliary contact is used, it must be positioned nearest the cam, in slot A shown above. A second auxiliary contact

would be positioned in slot B.

1.

Make sure the auxiliary contact and adapter kit (circuit breaker) have been installed in the proper position.

2. If the auxiliary contact (circuit breaker) is N.O., place the probes of the continuity tester across both terminals with the

disconnect handle in the OFF position; there should be no continuity.

3.

Move the disconnect handle to the ON position and place the probes of the continuity tester across both terminals; there

should be continuity.

4.

If the auxiliary contact (circuit breaker) is N.C., place the probes of the continuity tester across both terminals with the

disconnect handle in the OFF position; there should be continuity.

5.

Move the disconnect handle to the ON position and place the probes of the continuity tester across both terminals; there

should be no continuity.

Support
Bracket

Support
Plate

Base
Assembly

Bail

Slot A

Slot B

Cam