Connect the motor series field between s1, Verify that the jumper between terminals 3 – Rockwell Automation 1397 Open Chassis Dynamic Brake User Manual

Page 12

Advertising
background image

1397 Open Chassis Dynamic Brake

12

1397-5.15 March, 1999

181/L1

81

47 (+)

45 (–)

M

M

A1

M

ARMATURE
SUPPLY

1397 DRIVE

1397 DRIVE

DB RESISTORS

282

281

283

AC

INPUT

82

83

182/L2

182/L3

A1

A2

S2

S1

MOTOR ARMATURE

2

1

5

DBR

A2/S1

6

6

1FU

2FU

3FU

3

2 4 F1 F2

1

P6-5 P6-2

RRB1-5

RRB1-6

35-F2

37-F1

DBCR

13

FROM

FIELD

SUPPLY

14

M AUX

DYNAMIC BRAKE

TERMINAL BLOCK

MOTOR SHUNT FIELD

8

7

S2

2

A1 S2 DBR

A2/S1

4

3

MOTOR SERIES FIELD

For 1397-DB-B400L — B600L Kits
If You are Using DB with a Motor Series Field
— S1 connected to A2 — without an Inverting Fault CIrcuit Breaker . . .

Remove and lockout all power to the drive and follow the wiring diagram above.

Follow the wiring diagram above to connect the motor armature to the drive and Inverting Fault Circuit Breaker.

Remove the connector bar link at A2/S1, but retain the A2/S1 connection bar and all (4) mounting bolts.

Replace the (2) lower bar bolts removed previously. Torque to 23.00 N-m (200 lb.-in.).

Replace the upper A2/S1 terminal bar using the (2) upper bar bolts removed previously. Torque to 23.00 N-m
(200 lb.-in.).

Route customer supplied cable between A2/S1 and motor connection A2 or S1. Cable should be sized to the
same guage as the DB resistor cables.

Route the DB resistor cables through the grommeted hole in the resistor mounting panel. Connect to connection
bars DBR

&

A2/S1 at the top of the 1397 drive using the (2) M10 hex bolts, washers and KEP nuts supplied

with the kit. Torque to 23.00 N-m (200 lb.-in.).

Connect the motor series field between S1

&

S2.

Verify that the jumper between terminals 3

&

4 at the drive terminal block is installed.

Remove the lockout and reapply power. Refer to 1397-DB-B400L — B600L Dynamic Brake Kit
Operation
above and proceed to Setup on the last page.