Setup, Continued) p.272 e-fld volts adj parameter, A-c jumper settings – Rockwell Automation 1397 Enhanced Field Supply Csrd User Manual

Page 10: P.272 [e-fld volts adj

Advertising
background image

10

1397 Enhanced Field Supply Card

1397–5.12 June, 1997

0

1

2

3

4

5

6

7

8

9

000

0.9003

0.9004

0.9005

0.9006

0.9009

0.9012

0.9015

0.9020

0.9025

0.9031

010

0.9037

0.9045

0.9052

0.9061

0.9070

0.9080

0.9090

0.9102

0.9113

0.9126

020

0.9139

0.9153

0.9167

0.9182

0.9198

0.9214

0.9231

0.9248

0.9267

0.9285

030

0.9305

0.9325

0.9345

0.9366

0.9388

0.9410

0.9433

0.9456

0.9480

0.9505

040

0.9530

0.9555

0.9581

0.9608

0.9635

0.9662

0.9690

0.9719

0.9748

0.9777

050

0.9807

0.9837

0.9868

0.9899

0.9931

0.9963

0.9995

1.0028

1.0061

1.0095

060

1.0129

1.0162

1.0196

1.0229

1.0262

1.0294

1.0326

1.0358

1.0389

1.0420

070

1.0450

1.0480

1.0509

1.0538

1.0567

1.0595

1.0622

1.0649

1.0676

1.0702

080

1.0727

1.0752

1.0777

1.0801

1.0824

1.0847

1.8690

1.0891

1.0912

1.0932

090

1.0952

1.0972

1.0990

1.1009

1.1026

1.1043

1.1059

1.1075

1.1090

1.1104

100

1.1118

1.1131

1.1144

1.1156

1.1167

1.1177

1.1187

1.1196

1.1205

1.1213

110

1.1220

1.1226

1.1232

1.1237

1.1242

1.1245

1.1248

1.1251

1.1253

1.1254

120

1.1252

Setup

(continued)

P.272 E-Fld Volts Adj

Parameter

P.272 [E-Fld Volts Adj]

is used to match the drive’s rated field

voltage to different DC motor field voltages. A field voltage below the
motor’s rated value can operate the motor above rated base speed with
reduced torque. A voltage above the motor’s rated base speed however,
could also result in armature overvoltage and overheating of the motor’s
field windings.

Shown below and on the following page is the range of output motor field
voltages available using the Enhanced Field Supply Card. With the
Enhanced Field Supply Card, output voltage to the motor field is set equal
to the AC input line voltage times a line multiplier.

Where:

The Line Multiplier = The Motor Nameplate Field Voltage

AC Line Input Voltage

The following line multipliers correspond to an Enhanced Field Supply
jumper setting of either A-C or B-C. The shaded values shown
correspond to settings for parameter

P.272 [E-Fld Volts Adj]

as explained in the

example on the following page. Jumper J21 on the Drive’s Regulator
Board must then be set to match the calculated A-C or B-C range.

LINE

CT

707973-5R

SP4

582

583

581

F1/37

F2/35

FC3

B

CA

FC2

FC4

P4

P4

P4

X1

X2

H2

H1

A-C Jumper Settings

Enhanced Field Supply Jumper Set to A-C

Drive

Minimum Output

Maximum Output

Input Volts

Motor Field Volts

Motor Field Volts

230V AC

0.9V DC

1.12V DC

P.272

Advertising