Chapter 4, Applying power, Ch 4 - applying power – Rockwell Automation 1608P ProDySC Installation Instructions, 200 A User Manual

Page 15: Chapter

Advertising
background image

Rockwell Automation Publication 1608P-IN003A-EN-P - September 2013

15

Chapter

4

Applying Power

Before applying power to the ProDySC, make certain there are no metal
filings or any conductive debris in or on any components inside the
ProDySC.

Verify ProDySC voltage rating matches ac source voltage.

Ensure that all input/output wiring including grounding has been
completed, all covers are replaced, and that access doors are closed and
locked.

Place the ProDySC internal circuit breaker in the OFF position.

Apply power from the upstream branch protection device. Power will not
flow through to the load. The ProDySC touchscreen will become active.

Place the ProDySC internal circuit breaker in the ON position.

Ensure that the touchscreen displays "OK" in the upper left corner and
that the nominal voltage, current, and frequency in the status display are
correct.

If a "Critical" or "Fatal" system event appears on the touch screen call for
technical support.

Verify that the output (load) voltage is present and within its nominal
rating.

NOTICE: Cycling ProDySC input power in the sequence OFF--ON--OFF--ON within a one minute
period will cause a “Limit Cycle Timeout” alarm. In such case sag correction will be inhibited for
one minute, after which the alarm will automatically reset.

WARNING:

The ProDySC is interlocked. Opening ProDySC doors while the

system is in operation will trip the internal circuit breaker and result in loss of

power to protected loads.

ATTENTION:

For Information regarding the operation of ProDySC, including

information on the display screen and maintenance, see Publication 1608P-
UM003A-EN-P

Advertising