Hardwire UPS

Wiring of the UPS should be performed by a qualified electrician using the appropriate wire gauges.

Selection of Cables:

AC Main Input / Output Wiring for UPS:

Connect Power and Equipment to the UPS

1. Connect the appropriate input power to the UPS's input (Line, Neutral and Ground) terminals (see

Diagram 3).

2. Connect the specified equipment to the UPS's output (Line, Neutral and Ground) terminals (see

Diagram 3).

Diagram 3 - System Wiring

Item

Specification

Wire size

14 AWG

Minimum temperature

75°C

Wire conductor material

Copper only

Tightening torque for terminals

4.4 lb-in

Warning: To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent
protection in accordance with the National Electric Code, ANSI/NFPA 70.
A disconnect switch shall be provided by others for AC output circuit. To reduce the risk of fire, connect only to a circuit
provided with branch circuit overcurrent protection for 20 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70.

Warning: This UPS features Surge Protective Device (SPD) located on the top of the unit. Please disconnect all power
sources before servicing due to Electric Shock Hazard for risk of severe injury or death.'

INPUT

L

L

N

N

G

G

OUTPUT

AC Output

AC Input