1606-XLSRED Decoupling Module Instruction Manual / Bedienungsanleitung Entkopplungsmodul
1606-XLERED Redundancy Module Instruction Manual / Bedienungsanleitung Redundanzmodul

Examples and Recommendations for Redundant Applications

(see Fig. 16 to 20)

- Use separate input fuses for each power supply.
- Use 3-phase power supplies and gain functional safety if one phase fails.
- When

Single-phase power supplies are utilized connect them to different phases.

- It is desirable to set the output voltages of all power supplies to the same value (±0.5V) to

avoid a false signal of the DC-ok signal.

- Set power supplies to “Parallel Use” if this option is available.
- Use separate mains systems for each power supply whenever it is possible

Beispiele und Empfehlungen für redundante Anwendungen

(siehe Bild 16 bis 20)

- Für jede Stromversorgung sind eigene Sicherungen zu verwenden.
- Bei 3-Phasen-Systemen erreicht man einen zusätzlichen Schutz bei Ausfall einer Phase.
- Stromversorgungen mit 1-Phasen Eingang möglichst an unterschiedliche Phasen anschließen.
- Es ist wünschenswert die Ausgangsspannung der Stromversorgungen auf annähernd gleichen

Spannungswert (±0.5V) einzustellen um falsche DC-OK Signale der Netzgeräte zu vermeiden.

- Stromversorgungen auf „Parallel Use“ stellen, falls diese Option verfügbar ist.
- Es ist vorteilhaft für jede Stromversorgung ein separates Speisenetz zu verwenden.

Fig. 16 / Bild 16

1+1 Redundant system utilizing 1606-XLSRED: 10A system with two 10A power supplies /

1+1 Redundantes System mittels 1606-XLSRED: 10A System mit zwei 10A Stromversorgungen

Fig. 17 / Bild 17

1+1 Redundant system utilizing 1606-XLERED: 10A system with two 10A power supplies /

1+1 Redundantes System mittels 1606-XLERED: 10A System mit zwei 10A Stromversorgungen

Failure

Monitor

10A

Load

I

I

L

N

PE

L N PE

+ +

- -

1606-XLS240E

Power

Supply

24V,10A DC-

OK

L N PE

+ +

- -

1606-XLS240E

Power

Supply

24V,10A DC-

OK

1606-

XLSRED

Redundancy

Module

Input

1

Input

2

+

-

+

-

+

-

Output

Failure

Monitor

I

I

L

N

PE

+ +

- -

L N PE

1606-XLE240E

Power

Supply

24V,10A

10A

Load

Input

1

Input

2

+

-

+

-

1606-XLERED

Redundancy

Module

Input

1

Input

2

+

-

Output

+ +

- -

L N PE

1606-XLE240E

Power

Supply

24V,10A

Fig. 18 / Bild 18

1+1 Redundant system utilizing 1606-XLSRED40: 20A system with two 20A power supplies /

1+1 Redundantes System mittels 1606-XLSRED40: 20A System mit zwei 20A Stromversorgungen

Fig. 19 / Bild 19

1+1 Redundant system utilizing 1606-XLSRED80: 40A system with two 40A power supplies /

1+1 Redundantes System mittels 1606-XLSRED80: 40A System mit zwei 40A Stromversorgungen

L1
L2

PE

L3

Failure

Monitor

I

I

I

I

I

I

L1 L2 L3 PE

+ +

- -

1606-XLS480E-3

Power

Supply

24V,20A DC-

OK

L1 L2 L3 PE

+ +

- -

1606-XLS480E-3

Power

Supply

24V,20A DC-

OK

Output

Input

1

Input

2

+

-

+

-

+

-

1606-

XLSRED40

Redundancy

Module

20A

Load

L1
L2

PE

L3

L1 L2 L3 PE

1606-XLS960E-3

40A Power Supply

+ +

- -

24V, 40A

Parallel Use
Single Use

DC-

OK

Failure

Monitor

I

I

I

I

I

I

L1 L2 L3 PE

1606-XLS960E-3

40A Power Supply

+ +

- -

24V, 40A

Parallel Use
Single Use

DC-

OK

40A

Load

+

-

+

-

Input

1

Input

2

Output

+

-

1606-XLSRED80

Redundancy

Module

Fig. 20 / Bild 20

N+1 Redundant system: 120A with four 40A power supplies / N+1 Redundantes System: 120A mit vier 40A Stromversorgungen

L1 L2 L3 PE

1606-XLS960E-3

40A Power Supply

+ +

- -

24V, 40A

Parallel Use
Single Use

DC-

OK

120A

Load

Failure

Monitor

I

I

I

I

I

I

L1 L2 L3 PE

1606-XLS960E-3

40A Power Supply

+ +

- -

24V, 40A

Parallel Use
Single Use

DC-

OK

+

-

+

-

Input

1

Input

2

Output

+

-

1606-XLSRED80

Redundancy

Module

L1 L2 L3 PE

1606-XLS960E-3

40A Power Supply

+ +

- -

24V, 40A

Parallel Use
Single Use

DC-

OK

L1 L2 L3 PE

1606-XLS960E-3

40A Power Supply

+ +

- -

24V, 40A

Parallel Use
Single Use

DC-

OK

I

I

I

I

I

I

L1
L2

PE

L3

1606-XLSRED80

Redundancy

Module

+

-

+

-

Input

1

Input

2

Output

+

-

10000168677 (version 00)

PU-361.012.38-10A

Advertising