DIMENSIONS

C i r c u i t B r e a k e r

Dimensions in Inches I

Frame Size B

C E

A

D F G H J

Amperes Westinghouse ITE

ITE WEST ITE WEST ITE WEST.

100

EB,EHB,FB E,EF,EH 4

5

/16

3

5

/16

3

1

/4

4

1

/4

4

1

/8

4

15

/16

6

9

/16

6

3

/8

1

1

/16

7

3

/16

6

1

/4

7

13

/16

225

400

JA, KA

LB,LBB, HLB

F J

3

7

/8 -

-

3

7

/8

4

3

/8

6

15

/16

4

5

/8

7

1

3

/4

10

7

/8

6

11

1

/2

-

INSTALLATION INSTRUCTIONS

Operating Mechanism

NOTE: For ease of assembly it might be advisable to
install the circuit breaker operator and then the circuit

breaker.

1.

Remove nuts and washers from flange plate.

2.

Place the operating mechanism into the enclosure with

the operating handle in the ‘Off’ position. Tilt the
assembly under the flange and at the same time bring
the handle through the slot provided.

3.

Place flange plate studs through the holes in the flange

and mechanism frame while holding the assembly

against the under side of flange. Secure assembly to
flange.

4.

Attach operating mechanism mounting bracket firmly

to the enclosure mounting plate surface. See line

drawing Page

1

(Bolts and spacers are furnished by

user).

N O T E : I t i s r e c o g n i z e d t h a t h o l e s i n t h e e n c l o s u r e
mounting plate surface used to secure the circuit breaker

operating mechanism can be located previous to installa-

tion. Refer to line drawings on Page

2

.

Circuit Breaker Operator Mechanism

and Slide Mechanism

1.

Place the circuit breaker Operating Mechanism handle

in the “ON” position by first pushing the defeater

by-pass lever upward and then moving the operator
handle from “OFF” to “ON”.

2 .

P l a c e c i r c u i t b r e a k e r t o g g l e l e v e r i n t h e “ O N ”

position.

3.

Place circuit breaker Slide Mechanism on top of

breaker so that the slide bushings seat in the breaker
mounting holes, the toggle lever is through the slide

slot and the slot for receiving the bellcrank roller is
oriented

clockwise from the line side of the

circuit breaker terminals, as illustrated on Page

2

.

4.

5.

6 .

7.

8.

9.

10.

11.

NOTE: Loosen adjustment plate screws on slide

mechanism, when provided.

Insert the long mounting screws into the circuit
breaker mounting holes.

W E S T I N G H O U S E B R E A K E R W I T H E B , E H B , o r

FB FRAME ONLY. Secure adapter plate provided

w i t h S l i d e M e c h a n i s m K i t , o n t o t h e m o u n t i n g

bracket, as illustrated on Page

2

.

Position circuit breaker assembly obtained in steps 3
and 4 so that the breaker line terminals are toward
the “ON” direction of the Operating Mechanism

handle and the bellcrank roller (operating mecha-
nism) is in the bellcrank slot (slide mechanism).

Align the four circuit breaker mounting screws with
the proper tapped holes in the Operating Mechanism
frame mounting surface. See illustrations on Page

2

for ITE and Westinghouse mounting.

CAUTION: Position circuit breaker so that mounting
screws are perpendicular to mounting surface and
secure the breaker to Operating Mechanism frame by

tightening the mounting screws.

NOTE: The circuit breaker can be secured onto the
Operator Mechanism mounting frame either before or

after the Operator Mechanism has been secured to the
enclosure flange.

ITE BREAKER WITH FJ FRAME AND WESTING-

HOUSE BREAKER WITH JA FRAME ONLY. Ad-

just the drive plate on the slide, per instructions

provided on Slide Mechanism.

Move Operator Mechanism handle from “ON” to
“ O F F ” a n d t h e n f r o m “ O F F ” t o “ O N ” t o e n s u r e
proper mechanical and electrical operation.

C A U T I O N : P l a c e O p e r a t o r M e c h a n i s m h a n d l e i n

“OFF” position before installation of wiring, for

maximum safety.