Rockwell Automation 1606-XLS960 DC Power Supply User Manual

Page 6

Advertising
background image

10000172266

01

M. GUELMI

7-19-13

6

6

B

TECHNICAL DATA SHEET
BUL. 1606-XLS960EE, 1606-XLS960FE
POWER SUPPLIES

1606-XLS960: Power Supply Instruction Manual
1606-XLS960: Bedienungsanleitung für Stromversorgung

Terminals and Wiring

Use appropriate copper cables that are designed for a minimum operating temperature of:

60°C for ambient temperatures up to 45°C,

75°C for ambient temperatures up to 60°C and

90°C for ambient temperatures up to 70°C.

Follow national installation codes and regulations! Ensure that all strands of a stranded wire enter
the terminal connection! Ferrules are allowed.

Input Output

Signals

Solid

wire

0.5-6mm

2

0.5-16mm

2

0.15-1.5mm

2

Stranded

wire

0.5-4mm

2

0.5-10mm

2

0.15-1.5mm

2n

American wire gauge

AWG 20-10

AWG 22-8

AWG 26-14

Max.

wire

diameter 2.8mm

5.2mm

1.5mm

(including

ferrules)

Wire stripping length

7mm / 0.28inch

12mm / 0.5inch

7mm / 0.28inch

Tightening torque

1Nm / 9lb.inch

2.3Nm / 20.5lb.inch

Spring-clamp terminal

Anschlussklemmen und Verdrahtung

Verwenden Sie geeignete Kupferkabel, die mindestens für:

60°C bei einer Umgebungstemperatur bis zu 45°C,

75°C bei einer Umgebungstemperatur bis zu 60°C und

90°C bei einer Umgebungstemperatur bis zu 70°C zugelassen sind.

Beachten Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass
keine einzelnen Drähte von Litzen abstehen. Aderendhülsen sind erlaubt.

Eingang Ausgang Signale

Starrdraht

0,5-6mm

2

0,5-16mm

2

0,15-1,5mm

2

Litze

0,5-4mm

2

0,5-10mm

2

0,15-1,5mm

2

AWG

AWG 20-10

AWG 22-8

AWG 26-14

Max.

Drahtdurchmesser

2,8mm

5,2mm

1,5mm

(inklusive

Aderendhülsen)

Abisolierlänge

7mm / 0,28inch

12mm / 0,5inch

7mm / 0,28inch

Anzugsdrehmoment

1Nm / 9lb.inch

2.3Nm / 20,5lb.inch

Federkraftklemme

Indicators, LEDs

Overload LED

DC-OK LED

DC-OK Contact

Normal mode

OFF

ON

Closed

During BonusPower

®

OFF

ON

Closed

Overload (Hiccup mode)

flashing

OFF

Open

Output short circuit

flashing

OFF

Open

Temperature Shut-down

flashing

OFF

Open

Active Shut-down input

flashing

OFF

Open

Anzeigelampen

t

c

a

t

n

o

C

K

O

-

C

D

D

E

L

K

O

-

C

D

D

E

L

d

a

o

l

r

e

v

O


Normalbetrieb AUS

EIN

geschlossen

Während BonusPower

®

AUS

EIN

geschlossen

Überlast (Hiccup- Modus) blinken

AUS

offen

Ausgangskurzschluss blinken AUS

offen

Temperaturabschaltung blinken

AUS

offen

Aktiver „shut-down“ Eingang

blinken

AUS

offen

Fig. 8 / Bild 8

1606-XLS960E, 1606-XLS960F; Functional Diagram / Funktionsschaltbild

Fig. 9 / Bild 9

1606-XLS960EE, 1606-XLS960FE; Functional Diagram / Funktionsschaltbild

+

+

-
-

V

OUT

DC-ok
Contact

Output

Over-

Voltage

Protection

Bridgeless

PFC

Converter

Input Fuse
Input Filter
Inrush Limiter

Output

Voltage

Regulator

Power

Converter

Output

Filter

DC ok

Relay

Output

Voltage
Monitor

Output

Power

Manager

Temper-

ature

Shut-

down

Overload

LED

DC-ok

LED

N

L

Single /

Parallel

Shut-down

Input &

Remote

Control

Shut-
down

13

14

15

16

Event Datalogger

+

+

-
-

V

OUT

DC-ok
Contact

Output

Over-

Voltage

Protection

PFC

Converter

Input Fuse
Input Filter
Input Rectifier
Inrush Limiter

Output

Voltage

Regulator

Power

Converter

Output

Filter

DC ok

Relay

Output

Voltage
Monitor

Output

Power

Manager

Temper-

ature

Shut-

down

Overload

LED

DC-ok

LED

N

L

Single /

Parallel

Shut-
down

13

14

15

16

Event Datalogger

Shut-down

Input &

Remote

Control

Fig. 10 / Bild 10

1606-XLS960E, 1606-XLS960F; Dimensions / Abmessungen

Fig. 11 / Bild 11

1606-XLS960EE, 1606-XLS960FE; Dimensions / Abmessungen

10000172266 (version 01) PU-384.010.38-10A

Advertising