Installation Instructions

Bulletin 1494F Disconnect Handle for Disconnect Switches and Circuit Breakers

(Cat 1494F-M2; 1494F-S2)

WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or
damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.

A

B

B

A

Door Catch

Mounting

Bracket

Right Hand Flange

Left Hand Flange

Door Catch
Mounting
Bracket

1

-5/8”

1

-5/8”

1

-7/32”

MAX.

1

-7/32”

MAX.

3

-49/64”

3

-49/64”

1

Square corners

or up to

1/4" radius

(2) .328” Dia.

Holes

Locating and Drilling Handle Holes

Tools
Needed:

5”

1/2"

9/16"

1/4"

Switch Rating

Circuit Breaker

Frame Size

A

(MIN)

B

(MIN)

(MIN)

C

(MAX)

D

E

F

400 A

14-3/16”

1-1/8”

1-7/32”

1-5/8”

5/8”

5/8”

600 A

18-3/16”

1-1/8”

1-7/32”

1-5/8”

3/4”

3/4”

800 A

1200 A

To make slot,

drill (2) 1/2"

diameter holes

and remove burrs

Notes:

·

E

nclosures with a Flange Thickness less than 3/16" use dimensions shown on this instruction sheet.

·

E

nclosures with a Flange Thickness 3/16" and greater use dimensions in Mounting Kit 1494V-H6.

This kit requires “B” dimension of 1-7/32” minimum.

6

-1/2”

7/16”

21/64” (.328”)
and
1/2” (.500”)

Slotted
1/4” Wide Slot

File

Allen Wrench
1/8” (.125”)

* - Only needed for handle cutout

*

*

*