Rockwell Automation 1414-CTZxx_CTDxx_CTOxx_CTSxx_CTTxx_ITSxx_ITTxx_ITZxx_ITDxx_ITOxx_ITSxx_ITZxx_ITDxx Space Temperature Transmitter User Manual

Page 6

Advertising
background image

6 Space Temperature Transmitter

Publication 1414-IN012A-EN-P - October 2005

Operating Temperature

0 … 70°C (32 … 158°F)

Operating Humidity

0 … 95% RH (non-condensing)

4-20 mA Loop Power Supply

18 … 35 Vdc (with 250 ohm load and no LCD)

22 … 35 Vdc (with 250 ohm load and LCD)

Loop Current (Minimum)

2 mA nominal (occurs with shorted sensor)

Loop Current (Maximum)

22.5 mA nominal (occurs with open sensor)

Maximum Loop Load

> 600 ohms at 24 Vac/dc with no LCD,
> 325 ohms with LCD

Protection Circuitry

Reverse voltage protected and output limited

Display Accuracy

±0.2ºF over full range with respect to the output signal

Display Units

ºF (Factory set)

Display Range

32.0 … 95°F

Display Resolution

0.1ºF for display of 00.0 to 99.9

Slide-pot

20 – 30K (L-R)

Switch

Normally open pushbutton, 0.4 VA at 24 Vac/dc standard

Space Temperature Transmitter Specifications