Specifications – Rockwell Automation 1734-PDN/B Point I/O DeviceNet Communication Interface User Manual

Page 15

Advertising
background image

POINT I/O DeviceNet Communication Interface Module 15

Publication

1734-IN057D-EN-P - April 2005

Specifications

Communication Interface Specifications

Expansion I/O Capacity

Up to 17 modules, dependent on backplane bus current draw
(17 times 75mA = 1.275A, just under the limit of 1.3A)
The actual number of modules can vary.
Add up the current requirements of the modules you want to
use to make sure they do not exceed the amperage limit of
the 1734-PDN module.
Cat. No. POINTBus Current Requirements
1734-IB2

75mA

1734-IB4

75mA

1734-IB8

75mA

1734-IV2

75mA

1734-IV4

75mA

1734-OB2

75mA

1734-OB4

75mA

1734-OB8

75mA

1734-OB2E

75mA

1734-OB2EP

75mA

1734-OB4E

75mA

1734-OB8E

75mA

1734-OV2E

75mA

1734-OV4E

75mA

1734-OW2

80mA

1734-OW4 80mA
1734-OX2

100mA

1734-IE2C

75mA

1734-OE2C

75mA

1734-IE2V

75mA

1734-OE2V

75mA

1734-IA2

75mA

1734-IM2

75mA

1734-OA2

75mA

1734-IJ

160mA

1734-IK

160mA

1734-IR2

220mA

1734-IT2I

175mA

1734-SSI

110mA

1734-232ASC

75mA

1734-VHSC5

180mA

1734-VHSC24

180mA

1734-485ASC

75mA

Advertising