Dh-485 connections, Grounding and terminating the dh-485 network – Rockwell Automation 1747-AIC SLC 500 Programmable Controller Isolated Link Coupler User Manual

Page 2

Advertising
background image

Publication 1747-IN062A-MU-P - April 2003

2 SLC

®

500 Programmable Controller Isolated Link Coupler

DH-485 Connections

Connecting the Communication Cable to the Link Coupler

Attach the terminal block of the link coupler to the Belden #3106A or
#9842 cable as shown below.

Grounding and Terminating the DH-485 Network

Only one of the Link Couplers at the end of the link must have
Terminals 1 and 2 of the network connector jumpered together.

Link couplers at both ends of the network must have Terminals 5 and
6 of the link connectors jumpered together.

Use Belden #9842 shielded, twisted-pair cable.

Belden #3106A

Belden #9842

For this wire/pair

Connect this wire

To this terminal

For this wire/pair

Connect this wire

To this terminal

Shield/Drain

Non-jacketed

2 - Shield

Shield/Drain

Non-jacketed

2 - Shield

Blue

Blue

3 - Common

Blue/White

White with Blue Stripe

No connection - cut back

Blue with White Stripe

3 - Common

White/Orange

White with Orange Stripe

4 - Data B

White/Orange

White with Orange Stripe

4 - Data B

Orange with White Stripe

5 - Data A

Orange with White Stripe

5 - Data A

Belden #3106A or #9842

Shrink Tubing Recommended

Orange with White Stipes

White with Orange Stipes

Blue (#3106A) or Blue with White Stripes (#9842) Drain Wire

to Previous Device

to Successive Device

6 Termination
5 A

4 B
3 Common

2 Shield
1 Chassis Ground

6 Termination
5 A

4 B
3 Common

2 Shield
1 Chassis Ground

Multiple Connections

Single Connection