Rockwell Automation 1732D-8X81212D DNet ArmorBlock Network and Auxiliary Powered I/O Module IN User Manual
Page 18
Advertising
18 DeviceNet ArmorBlock Network and Auxiliary Powered I/O Module
Publication
1732D-IN009A-EN-E - April 2009
EFT/B Immunity
IEC 61000-4-4:
±3 kV at 5 kHz on power ports
±3 kV at 5 kHz on signal ports
±2 kV at 5 kHz on communications ports
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communications
ports
Conducted RF
immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Environmental Specifications (Continued)
Attribute
Value
Advertising