Specifications – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output User Manual

Page 19

Advertising
background image

1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 19

Publication 1732E-IN006C-EN-E - June 2013

Specifications

I/O status

Off

The input or output channel is inactive, can be calibrated.

Flashing Green

Channel is calibrating.

Green

1732E-IF4M12R – Normal operation, inputs being scanned.
1732E-OF4M12R – The output is active and under control.

Flashing Red

1732E-IF4M12R – Fault. Channel is at end of range.
1732E-OF4M12R – Output fault. The output is open (current
mode only), or a low/high clamp alarm is present.

Red

1732E-OF4M12R – Auxiliary power disconnected or off.

IMPORTANT

The Module Status LED indicator will flash red and green for a maximum
30 s while the module completes its POST (Power-On Self Test).

General Specifications

Attributes

Value

Voltage, power, max

30V DC

Voltage, power, min

12V DC

Module power

12…30V DC @ 300 mA

Power consumption

3 W @ 24V DC, typical

3.5 W, max (module unloaded)

Isolation voltage

50V (continuous), Basic Insulation Type

Type tested @ 707V DC for 60 s

Communication rate

EtherNet/IP

10/100 Mbps

Full or half-duplex

100 meter per segment

Status indicators

Module status – red/green

Network status – red/green

Link status – green/yellow

Auxiliary power status – green

I/O LED – red/green

Indicator Status for Modules

Indicator

Status

Description

Advertising